50
PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
Refer to the section
Report IP Service
in the Protege System Controller Reference Manual
(227-4045-500).
All ULC S559 applications must transmit signals simultaneously over both the Contact ID Reporting
Service and the Report IP Service. This will occur automatically with the above programming.
The area Trouble Area must be armed. Refer to the section
Regular Arming
in the Protege System
Controller Reference Manual (227-4045-500)
In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time
must be set to 20 seconds. Please refer to the section
Poll/Grace Time
in the ArmorIP Internet Monitoring
Application User Manual (227-5500-000).
Central Station Signal Receiver
The maximum number of signal transmitting units connected to any transmission channel shall conform to
the manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous
connections.
Please refer to the section
Internet Connections Requirements
in the ArmorIP Receiver Installation Manual
(227-5510-000) for further details.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a
minimum of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the
sequence is reached, an indication of the failure shall be made at the premises.
In the Protege System, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The following options are required:
The Dialing Attempts option must be programmed. Please refer to the section
Dialing Attempts
in the
Protege System Controller Reference Manual (227-4045-500)
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Zone Service Test Report
Test report time must be programmed. Please refer to the section
Miscellaneous Options
in the
Protege System Controller Reference Manual (227-4045-500)
The Panel Option 5 (Option 5 - Generate Trouble Zone Test Report Restore) must be enabled. Please
refer to the section
Panel Options Generate Trouble Zone Test Report Restore
in the Protege System
Controller Reference Manual (227-4045-500)
The Panel Option 2 (Option 2 - Generate Test Report by Time of Day) must be enable. Please refer to
the section
Panel Options
in the Protege System Controller Reference Manual (227-4045-500)
Ethernet Connections
All Ethernet network connections shall be installed within the same room as the equipment.
Telephone Lightning Surge Protector
Telephone lightning surge protector manufactured by L-com Inc (Model HGLN-D1-DT) shall be connected
inline to the telephone dialer T1i and R1i. Refer to the PRT-CTRL-SE wiring diagram (see page 9) of this
manual.
Hardwire Transformer Marcus M4758CT
When installed with the power supply manufactured by Marcus, Model M4758CT:
The Digital Security Controls (DSC) Model ULC-LA power indicator light assembly (Installation
Instruction No. 29001877 R0) must be installed within a conduit knockout of either the ICT Model
CAB-LARGE-UL or Bosch Model D8108A enclosure in order to provide green AC power on indication.
The Littelfuse Part No. 150322 fuseholder and Littelfuse Part No. 0312005 5A, 3AG fast-acting fuse
must be installed in-line to the Models PRT-CTRL-SE, PRT-ZX16-PCB, and PRT-RDI2-PCB.
Fire Zones
Fires zones shall be separated from burglar zones through area partitioning.