UL and ULC Installation Requirements
i
Only UL / ULC listed compatible products are intended to be connected to a UL / ULC listed control
system.
16.1
Central Station Signal Receiver Compatibility List
IP Receiver via Ethernet Port : Integrated Control Technology ArmorIP Internet Monitoring Receiver. Serial
interface to be used with SIMS II version 1.3x central station automation system software and compatible
receiving equipment as indicted in the SIMS II Appendix E UL Supplement.
CID Receiver via Onboard Modem: Any UL and ULC listed receiver that uses the Contact ID protocol.
16.2
ULC Compliance Requirements
CAN/ULC-S304-06
Auto Arming
Control units that support auto arming shall provide an audible signal throughout the protected area not less
than 10 min prior to the auto arming taking place. The control unit shall allow authorized users to cancel the
auto arming sequence and transmit such cancelation to the signal receiving center with the identification of
the authorized user that canceled the action.
The following options must be enabled in the Protege System when using the Auto Arming feature. When
the defer warning time is programmed to 10 minutes, the PGM group will be activated 10 minutes before
the system performs the Auto Arming in the associated Area.
The Defer PGM or PGM Group must be programmed. Please refer to the section
Defer PGM or PGM
Group
in the Protege System Controller Reference Manual (227-4045-500) for programming
instructions. For details on modifying the Defer PGM or PGM Group, refer to the section
PGM and PGM
Group Entry
in the Protege System Controller Reference Manual (227-4045-500).
The Defer Warning Time must be programmed to not less than 10 minutes. Please refer to the section
Defer Arming Warning Time
in the Protege System Controller Reference Manual (227-4045-500).
The Defer Automatic Arming arming option must be enabled. Please refer to the section
Area Special
Options
in the Protege System Controller Reference Manual (227-4045-500)
Double EOL Zone Configuration
Only double EOL Zone Configuration shall be used. Please refer to the section
Inputs
(see page 24) of this
manual and the section
Zone Special Options
in the Protege System Controller Reference Manual
(227-4045-500).
Multiplex System and Poll Time
The PRT-CTRL-SE is compatible with the Integrated Control Technology ArmorIP Internet Monitoring
Receiver. Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds.
In the Protege System, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
The Enable Poll Events option must be enabled. Please refer to option 5 in the section
Reporting
Options
in the Protege System Controller Reference Manual (227-4045-500)
The Poll Time must be programmed to 40 seconds. Please refer to the
Poll Time
section in the Protege
System Controller Reference Manual (227-4045-500)
Central Station Signal Receiver
The common equipment of each signal receiving center control unit shall be limited to 1000 alarm systems.