PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
29
8
Hardware Configuration
8.1
Configuration Switch
The Controller uses a 4 way dual inline dip switch located in the centre of the PCB board. This switch is used to
configure the boot up and power on settings for the Controller. Each of the switch positions performs a different
function. For normal operation, all switches shall be in the off position.
BOOT MODE 1
BOOT MODE 2
BIOS COMMUNICATION
DEFAULT CONTROLLER
1
2
3
4
ON
OFF
Configuration Switch
Switch
Switch
Function
1
2
Power Up Boot Mode
OFF
OFF
Normal Operation
ON
OFF
BOOT Loader
OFF
ON
BIOS Utility
ON
ON
Reserved Do Not Set
Switch
Switch
Function
3
-
IP Address Configuration
OFF
-
Programmed IP Configuration
ON
-
IP will be set to 192.168.111.222 while this switch remains on.
Allows the connection and review of the programmed IP address or
the modification to another setting.
Switch
Switch
Function
4
-
System Default
OFF
-
Normal Operation
ON
-
Factory Default Protege Controller