PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a
minimum of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the
sequence is reached, an indication of the failure shall be made at the premises.
In the Protege System, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The following options are required:
The Dialing Attempts option must be programmed. Please refer to the section
Dialing Attempts
in the
Protege System Controller Reference Manual (227-4045-500)
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Zone Service Test Report
Test report time must be programmed. Please refer to the section
Miscellaneous Options
in the
Protege System Controller Reference Manual (227-4045-500)
The Panel Option 5 (Option 5 - Generate Trouble Zone Test Report Restore) must be enabled. Please
refer to the section
Panel Options Generate Trouble Zone Test Report Restore
in the Protege System
Controller Reference Manual (227-4045-500)
The Panel Option 2 (Option 2 - Generate Test Report by Time of Day) must be enable. Please refer to
the section
Panel Options
in the Protege System Controller Reference Manual (227-4045-500)
ArmorIP automatically detects the reception of any invalid packet on the programmed port as a potential
system compromise attempt. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event in the Events Tab.
The event is sent with the following details:
Account Code as defined in the Account settings on the Ademco 685 tab of the Preferences Menu
Event Code 0x163
Group Code as defined in the Details settings on the Ademco 685 tab of the Preferences Menu
Point Code as defined in the Details settings on the Ademco 685 tab of the Preferences Menu
Refer to the section
Ademco 685
in the ArmorIP Internet Monitoring Application User's Manual
(227-5500-000).
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the Compromise Attempt event.
The telephone lightning surge protector manufactured by L-com Inc (Model HGLN-D1-DT) shall be
connected inline to the telephone dialer T1i and R1i of the PRT-CTRL-SE. Refer to the wiring diagram (see
page 9) of the PRT-CTRL-SE Installation Manual (227-4045-001).
When installed with the power supply manufactured by Marcus, Model M4758CT:
The Digital Security Controls (DSC) Model ULC-LA power indicator light assembly (Installation
Instruction No. 29001877 R0) must be installed within a conduit knockout of either the ICT Model
CAB-LARGE-UL or Bosch Model D8108A enclosure in order to provide green AC power on indication.
The Littelfuse Part No. 150322 fuseholder and Littelfuse Part No. 0312005 5A, 3AG fast-acting fuse
must be installed in-line to the Models PRT-CTRL-SE, PRT-ZX16-PCB, and PRT-RDI2-PCB.
UL294
The Models PRT-CTRL-SE and PRT-RDI2-PCB are intended to be mounted within the Model
CAB-LARGE-UL enclosure, installed inside the protected premise, and are UL 294 Listed for Attack Class I
applications only
Exit devices and wiring must be installed within the protected area.
System must be installed with at least one PRX-NPROX reader. For UL 294 Listed installations, the
PRX-NPROX, HID Model ProxPoint (6005BGB00) and iClass R40 (6120CKN0000) readers may be used.
For the Models PRT-CTRL-SE and PRT-RDI2-PCB, all RS485 and reader terminal connections must be
made using shielded, grounded cable.
The Model PRX-NPROX must be connected with shielded, grounded cable.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
Must be installed with UL 1034 Listed electronic locks for UL installations.