8
PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
3
Mounting
The Protege Controller is supplied as a PCB only (printed circuit board). We recommend that gear plate style
enclosures are used wherever possible, as this provides the best mounting and installation solution as well as
the required cable entry and termination space.
When installing the Controller ensure that there is adequate clearance around all sides of the cabinet enclosure
and air flow to the vents of the enclosure are not restricted.
It is recommended the Controller is installed in a location that will facilitate easy access for wiring. It is also
recommended that the Controller be installed in electrical rooms, communication equipment rooms, closets or
in an accessible area of the ceiling.
1.
Insert the plastic standoffs into the locations to mount the PCB board.
2.
Calculate the location and position of the cabinet enclosure and mark the holes for the keyhole points in the
top left and right locations. This will enable you to fasten the screws and then hang the box on them
adjusting the location to suit.
3.
Ensure a solid fixing point and fasten the two screws. Before tightening the top screws, insert the tamper
bracket in the slot provided on the right side of the cabinet enclosure.
4.
Fix the cabinet enclosure securely using the remaining mounting holes on the bottom left, right and centre
of the cabinet enclosure.
5.
If you are extending the Protege Controller by the addition of a communications module or memory
interface, insert the 4 extended nylon standoffs through the rear of the Controller.
6.
Insert the PCB into the cabinet enclosure and mount using the plastic standoffs inserted during step 1.
i
To reduce the risk of damage caused by debris during the installation, install the cabinet enclosure
when the circuit board is not installed on the plastic standoffs.
3.1
UL/ULC Installation Cabinet Options
UL/ULC Central Station Fire Monitoring, Central Station Alarm Installations
Cabinet Model
Manufacturer
UL/ULC Installation Listings
D8108A
Bosch
UL1610, UL1635, ULC-S304, ULC-S559
Electronic Access Control System Installations
UL
ULC
All cabinet installations of this type must be located inside the Protected Area.
Cabinet Model
Manufacturer
UL/ULC Installation Listings
CAB-LARGE-UL
ICT
UL294, CAN/ULC-S319
D8108A
Bosch
UL294, CAN/ULC-S319