Gas-Fired Water Boilers – 

Boiler Manual

2

Part Number 670 01 1001 00

Installations must follow these codes:

Local, state, provincial, and national codes, laws, regulations
and ordinances.

National Fuel Gas Code, ANSI Z223.1–latest edition.

Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1, when required.

National Electrical Code.

For Canada only: B149.1 or B149.2 Installation Code, CSA
C22.1 Canadian Electrical Code Part 1 and any local codes.

Certification

The GWA boiler gas manifold and controls met safe
lighting and other performance criteria when boiler
underwent tests specified in ANSI Z21.13–latest
edition.

Before locating the boiler:

Check for nearby connection to:

System water piping

Venting connections

Gas supply piping

Electrical power

Check area around boiler. Remove any combustible materials,
gasoline and other flammable liquids.

Failure to keep boiler area clear and free of
combustible materials, gasoline and other flammable
liquids and vapors can result in severe personal
injury, death or substantial property damage.

Boiler must be installed so that gas control system components
are protected from dripping or spraying water or rain during
operation or service.

If new boiler will replace existing boiler, check for and correct
system problems, such as:
1. System leaks causing oxygen corrosion or section cracks

from hard water deposits.

2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler

to freeze and leak.

Codes & checklist

Failure to adhere to the guidelines below can
result in severe personal injury, death or
substantial property damage.

When servicing boiler —

1. To avoid electric shock, disconnect electrical supply

before performing maintenance.

2. To avoid severe burns, allow boiler to cool before

performing maintenance.

Boiler operation —

3. Do not block flow of combustion or ventilation air to boiler.

4. Should overheating occur or gas supply fail to shut off, do

not turn off or disconnect electrical supply to circulator.
Instead, shut off the gas supply at a location external to
the appliance.

5. Do not use this boiler if any part has been under water.

Immediately call a qualified service technician to inspect
the boiler and to replace any part of the control system
and any gas control that has been under water.

Boiler water —

6. DO NOT use petroleum-based cleaning or sealing

compounds in boiler system. Water seal deterioration will
occur, causing leakage between boiler sections, circulator
flanges, diaphragm tanks or other system components.
This can result in substantial property damage.

7. DO NOT use "homemade cures" or "boiler patent

medicines". Serious damage to boiler, personnel and/or
property may result.

8. Continual fresh makeup water will reduce boiler life. Mineral

buildup in sections reduces heat transfer, overheats cast
iron, and causes section failure. Addition of oxygen and
other gases can cause internal corrosion. Leaks in boiler
or piping must be repaired at once to prevent makeup
water.

9. Do not add cold water to hot boiler. Thermal shock can

cause sections to crack.

Glycol — potential fire hazard —

All glycol is flammable when exposed to high temperatures. If
glycol is allowed to accumulate in or around the boiler or any
other potential ignition source, a fire can develop. In order to
prevent potential severe personal injury, death or substantial
property damage from fire and/or structural damage:

Never store glycol of any kind near the boiler or any
potential ignition source.

Monitor and inspect the system and boiler regularly for
leakage. Repair any leaks immediately to prevent possible
accumulation of glycol.

Never use automotive antifreeze or ethylene glycol in the
system. Using these glycols can lead to hazardous
leakage of glycol in the boiler system.

1

Prepare boiler location

Read this first!

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

35

Part Number 670 01 1001 00

Install GWA boilers for residential radiant panel systems, converted gravity
heating systems or other low water temperature applications per instructions
in this manual to avoid damage due to condensation.
GWA boilers are CSA design certified for installation on combustible
flooring.
GWA boilers are ASME rated for 50 psig working pressure.

14 Ratings

DOE

1. Based on standard test procedures prescribed by the United States Department of

Energy.

2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the

requirements of the building and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15. An additional allowance
should be made for unusual piping and pickup loads.

3. See information at right for model number suffixes. Letters shown are model number

suffixes. An “N” after the model number designates natural gas. The letter after the
“N” designates the pilot ignition system —  “S” for standing pilot or “I” for spark-
ignited pilot. For example, a suffix “NS” means a natural standing pilot boiler.

4. Contact your International Comfort Products dealer regarding information and parts

for high altitude applications.

Boiler

model

number

0–2,000 feet altitude

2,000–4,500 feet altitude

(Canada)

Net

I=B=R

ratings

(Btuh)

Boiler
water

content
(gallons)

DOE

Seasonal

efficiency

(% A.F.U.E)

Chimney

and

breeching

size

Input

(Btuh)

DOE Heating Capacity

(Output) (Btuh)

Input

(Btuh)

Output

(Btuh)

NS

NI

(Note 3)

(Note 1)

(Note 4)

(Note 2)

(Note 3)

GWA052

52,000

43,000

46,800

37,400

37,000

1.5

80.2

83.0

4"I.D. x 20’

GWA070

70,000

58,000

63,000

50,400

50,000

1.5

80.1

82.2

4"I.D. x 20’

GWA105

105,000

88,000

94,500

75,600

77,000

2.1

80.4

82.9

5"I.D. x 20’

GWA140

140,000

117,000

126,000

100,800

102,000

2.7

80.4

82.5

6"I.D. x 20’

GWA175

175,000

145,000

157,500

126,000

126,000

3.3

80.5

82.2

6"I.D. x 20’

GWA210

210,000

175,000

189,000

151,200

151,000

3.8

80.5

81.8

7"I.D. x 20’

GWA245

245,000

202,000

220,500

176,400

176,000

4.4

80.5

81.4

7"I.D. x 20’

Содержание GWA 245

Страница 1: ...Hazards that will or can cause minor personal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property...

Страница 2: ......

Страница 3: ...ation dimensions Residential garage installation Take the following special precautions when installing the boiler in a residential garage If the boiler is located in a residential garage per ANSI Z22...

Страница 4: ......

Страница 5: ...n 12 inches of the ceiling the other within 12 inches of the floor as shown in the table illustrations Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk o...

Страница 6: ......

Страница 7: ...ded with boiler 7 Temporarily plug the air elimination tapping next to supply tapping 2 Prepare boiler continued Pressure test Fill and pressure test 1 Open the shutoff valves you installed on supply...

Страница 8: ......

Страница 9: ...the damper blade 3 Install damper harness between damper actuator and hole in jacket left side panel See Figure 3 page 8 Use strain relief connectors and locknuts to secure both ends of damper harnes...

Страница 10: ......

Страница 11: ...ation Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners resulting in severe personal injury death or substantial property damage Ins...

Страница 12: ......

Страница 13: ...8 79 150 305 460 150 31 64 120 250 380 1 Remove jacket front panel and see Figure 10 to pipe gas to boiler a Install drip leg at inlet of gas connection to boiler Where local utility requires drip leg...

Страница 14: ......

Страница 15: ...ragm type or bladder type expansion tank systems only one turn 5 Open other vents a Starting on the lowest floor open air vents one at a time until water squirts out b Repeat with remaining vents 6 Re...

Страница 16: ......

Страница 17: ...to verify operation 5 Return thermostat to normal setting 6 Set thermostat heat anticipator setting indicated on wiring diagram Check venting system operation 1 With boiler firing hold a candle or mat...

Страница 18: ......

Страница 19: ...d on boiler Vent damper will remain closed until a call for heat 2 Call for heat When thermostat circuit closes the boiler circulator and vent damper are energized The vent damper drives open When the...

Страница 20: ......

Страница 21: ...inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowes...

Страница 22: ......

Страница 23: ...lace it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fre...

Страница 24: ......

Страница 25: ...tomatic air vents in systems with closed type tanks The air will escape from the system instead of returning to the tank Eventually the tank will waterlog and no longer control pressurization The boil...

Страница 26: ......

Страница 27: ...ow Lighting Instructions pages 20 and 21 If gas is available and you cannot obtain a pilot flame try purging the gas line and cleaning pilot and pilot gas tubing Follow Lighting Instructions again If...

Страница 28: ......

Страница 29: ...2 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 450021270WT 450021271WT 450021272WT 450021273WT 450021274WT 450021275WT 450021276WT Item number Description International Comfort Products part number 4 Hig...

Страница 30: ......

Страница 31: ...T 4 Jacket panel door GWA052 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 431223450WT 431223451WT 431223452WT 431223453WT 431223454WT 431223455WT Item number Description International Comfort Products pa...

Страница 32: ......

Страница 33: ...rt number Standing pilot Natural gas components 1 Gas valve 1 2 x 1 2 GWA052 through GWA175 Gas valve 3 4 x 3 4 GWA210 and GWA245 Honeywell Robertshaw Honeywell VR8200A2116 7200ER VR8300C4050 51104436...

Страница 34: ......

Страница 35: ...after the model number designates natural gas The letter after the N designates the pilot ignition system S for standing pilot or I for spark ignited pilot For example a suffix NS means a natural sta...

Страница 36: ......

Отзывы: