GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

10

Part Number 670 01 1001 00

Table 4

Water pipe size (based on 20 °F rise)

General

If installation is to comply with ASME or Canadian requirements,
an additional high temperature limit is needed. Install control in supply
piping between boiler and isolation valve. Set second control to
minimum 20 °F above setpoint of first control. Maximum allowable
setpoint is 240 °F. See page 19 for wiring.

A low water cutoff device is required when boiler is installed above
radiation level or by certain state or local codes or insurance
companies. Use low water cutoff designed for water installations.
Electrode probe-type is recommended. Purchase and install in tee
supply piping above boiler.

Use backflow check valve in cold water supply if required by local
codes.

See Table 4 and Figure 5 (diaphragm-type or bladder-type expansion
tank) or Figure 6 (closed-type expansion tank) on page 11 for near-
boiler piping for systems designed for return water at least 130 °F.

See page 12 (Figures 8 and 9) for near-boiler piping for low-
temperature or high-volume systems.

See page 11 (Figure 7) for boilers used with refrigeration systems.

Near-boiler piping

3

Install water piping

Relief valve

Install relief valve vertically in ¾" tapping on side of boiler. See the
tag attached to the relief valve for manufacturer’s instructions.

To avoid water damage or scalding due to valve
operation, discharge line must be connected to relief
valve outlet and run to a safe place of disposal.
Terminate the discharge line to eliminate possibility
of severe burns should the valve discharge.

• Discharge line must be as short as possible and be

the same size as the valve discharge connection
throughout its entire length.

• Discharge line must pitch downward from the valve

and terminate at least 6" above the floor drain where
any discharge will be clearly visible.

• The discharge line shall terminate plain, not threaded,

with a material serviceable for temperatures of 375 °F
or greater.

• Do not pipe the discharge to any place where freezing

could occur.

• No shutoff valve shall be installed between the relief

valve and boiler, or in the discharge line. Do not plug
or place any obstruction in the discharge line.

• Failure to comply with the above guidelines could

result in failure of the relief valve to operate, resulting
in possibility of severe personal injury, death or
substantial property damage.

• Test the operation of the valve after filling and

pressurizing system by lifting the lever. Make sure
the valve discharges freely. If the valve fails to operate
correctly, replace it with a new relief valve.

Water piping — multiple zone systems

Install system piping using either circulator zoning or zone valve
zoning. Install expansion tank on suction side of system circulator.
Always connect fill line only at the expansion tank — never at
another point in the system.

Circulator

The circulator is shipped loose (wiring pre-attached to boiler) to
allow you to locate it either in the return or supply piping, as desired.
See page 11 for a typical installation. Pipe the expansion tank to
the suction side of the circulator whenever possible. Install an air
separator in the supply piping. Connect the expansion tank to the
air separator only if the separator is on the suction side of the
circulator. Always install the system fill connection at the same point
as the expansion tank connection to the system. Figures 5 and 6
show typical near-boiler piping connections.

Expansion tank

Diaphragm-type or bladder-type expansion tank —
Figure 5

1. Ensure expansion tank size will handle boiler and system water

volume and temperature. Tank must be located in boiler return
piping as close to boiler as possible, before inlet side of circulator.
See tank manufacturer’s instructions for details.

2. Install an automatic air vent as shown.

Closed-type expansion tank — Figure 6

1. Ensure expansion tank size will handle boiler and system water

volume and temperature. See tank manufacturer’s instructions
for details.

2. Connect tank to ½" NPT tapping located behind supply outlet,

using ½" NPT piping. Pitch any horizontal piping up towards
tank 1 inch per 5 feet of piping.

Undersized expansion tanks cause system water to
be lost from relief valve and makeup water to be
added through fill valve. Eventual section failure can
result.

Near-boiler piping 

continued

Boiler model

number

To

system

From

system

GWA052

¾"

¾"

GWA070

1"

1"

GWA105

1"

1"

GWA140

1"

1"

GWA175

1¼"

1¼"

GWA210

1¼"

1¼"

GWA245

1½"

1½"

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

27

Part Number 670 01 1001 00

11 Troubleshooting

Verify proper operation after servicing.  • See vent
damper manufacturer’s instructions packed with vent
damper for additional information. Failure to comply
could result in severe personal injury, death or
substantial property damage.

Figure 15

Manually opening vent damper

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
Never jumper (bypass) rollout thermal fuse element
or any other device except for momentary testing as
outlined in “Chart 1”, page 28. Severe personal injury,
death or substantial property damage can result.
Burner access panel must be in position during boiler
operation to prevent momentary flame rollout on
ignition of main flame. Severe personal injury or
substantial property damage will result.

Before troubleshooting:

1. Have the following items:

a. Voltmeter that can check 120 VAC and 24 VAC.
b.

Microammeter with a scale range of 0-10.

c. Continuity checker.
d. U-tube manometer.

2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC)

to boiler.

3. Make sure thermostat is calling for heat and contacts (including

appropriate zone controls) are closed. Check for 24 VAC
between thermostat wire nuts and ground.

Troubleshooting sequence:

1. Before proceeding, check for:

Loose connections, blown fuse or service switch off?

High limit switch set below boiler water temperature?

Thermostat set below room temperature?

Gas not turned on at meter or boiler?

Incoming gas pressure less than:
5" w.c. for natural gas?  11" w.c. for propane gas?

2. If all of the above check correctly, check gas pressures:

a. With boiler off

13" w.c. maximum natural or propane gas pressure
upstream of gas valve.

b.

With boiler on:

5" w.c. minimum natural gas pressure or 11" w.c.
propane gas pressure upstream of gas valve.

3.5" w.c. minimum natural gas pressure or 10" w.c.
propane gas pressure downstream tapping on gas
valve — Can be adjusted by regulator on gas valve.

c. If gas pressure is incorrect or gas is not available to boiler,

contact gas supplier to correct before proceeding further.

3. Check pilot operation - Follow “Lighting Instructions”, pages 20

and 21.

If gas is available and you cannot obtain a pilot flame, try
purging the gas line and cleaning pilot and pilot gas tubing.
Follow “Lighting Instructions” again. If you still cannot obtain
a flame, replace pilot burner and gas tubing. If this does not
allow you to obtain a pilot flame, replace gas valve.

If you obtain a pilot flame, but pilot will not remain on, replace
thermocouple. If this does not correct problem, replace gas
valve and pilot burner.

If pilot stays on, but main gas will not come on, proceed to
page 28.

In event of vent damper failure:

Effikal vent damper

If troubleshooting chart recommends replacing actuator and actuator
is not immediately available, damper blade can be fixed in an open
position to allow boiler operation. Manually turning blade can cause
actuator damage. Follow these instructions only in case of no heat
or damper actuator malfunction.

1.

Move damper service switch to Hold Damper Open position.
Apply call for heat to boiler. Damper blade should then rotate to
Open position and boiler will fire.

2. If step 1 does not open damper, manually rotate damper blade

to open position using wrench or pliers on flat shaft between
damper and actuator. Boiler will fire. Verify that damper service
switch is in Hold Damper Open position. (Figure 15)

3. Do not leave vent damper permanently in this position. Replace

actuator immediately. If vent damper is left in Open position,
boiler will not operate at published efficiencies.

Johnson Controls vent damper

If troubleshooting chart recommends replacing actuator and actuator
is not immediately available, damper blade can be fixed in an open
position to allow boiler operation. Follow these instructions only in
case of no heat or damper actuator malfunction. See Figure 15.

1. Turn off power to boiler.

Failure to turn off power to boiler can result in severe
personal injury, death or substantial property damage.

2. See vent damper manufacturer’s instructions for procedure to

fix vent damper in open position.

3. Turn on power to boiler.

4. Using wrench or pliers on flat shaft section, manually rotate

damper blade until green light turns on. Boiler will fire. (Figure 15)

5. Do not leave vent damper permanently in this position. Replace

actuator immediately. If vent damper is left in Open position,
boiler will not operate at published efficiencies.

Содержание GWA 245

Страница 1: ...Hazards that will or can cause minor personal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property...

Страница 2: ......

Страница 3: ...ation dimensions Residential garage installation Take the following special precautions when installing the boiler in a residential garage If the boiler is located in a residential garage per ANSI Z22...

Страница 4: ......

Страница 5: ...n 12 inches of the ceiling the other within 12 inches of the floor as shown in the table illustrations Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk o...

Страница 6: ......

Страница 7: ...ded with boiler 7 Temporarily plug the air elimination tapping next to supply tapping 2 Prepare boiler continued Pressure test Fill and pressure test 1 Open the shutoff valves you installed on supply...

Страница 8: ......

Страница 9: ...the damper blade 3 Install damper harness between damper actuator and hole in jacket left side panel See Figure 3 page 8 Use strain relief connectors and locknuts to secure both ends of damper harnes...

Страница 10: ......

Страница 11: ...ation Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners resulting in severe personal injury death or substantial property damage Ins...

Страница 12: ......

Страница 13: ...8 79 150 305 460 150 31 64 120 250 380 1 Remove jacket front panel and see Figure 10 to pipe gas to boiler a Install drip leg at inlet of gas connection to boiler Where local utility requires drip leg...

Страница 14: ......

Страница 15: ...ragm type or bladder type expansion tank systems only one turn 5 Open other vents a Starting on the lowest floor open air vents one at a time until water squirts out b Repeat with remaining vents 6 Re...

Страница 16: ......

Страница 17: ...to verify operation 5 Return thermostat to normal setting 6 Set thermostat heat anticipator setting indicated on wiring diagram Check venting system operation 1 With boiler firing hold a candle or mat...

Страница 18: ......

Страница 19: ...d on boiler Vent damper will remain closed until a call for heat 2 Call for heat When thermostat circuit closes the boiler circulator and vent damper are energized The vent damper drives open When the...

Страница 20: ......

Страница 21: ...inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowes...

Страница 22: ......

Страница 23: ...lace it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fre...

Страница 24: ......

Страница 25: ...tomatic air vents in systems with closed type tanks The air will escape from the system instead of returning to the tank Eventually the tank will waterlog and no longer control pressurization The boil...

Страница 26: ......

Страница 27: ...ow Lighting Instructions pages 20 and 21 If gas is available and you cannot obtain a pilot flame try purging the gas line and cleaning pilot and pilot gas tubing Follow Lighting Instructions again If...

Страница 28: ......

Страница 29: ...2 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 450021270WT 450021271WT 450021272WT 450021273WT 450021274WT 450021275WT 450021276WT Item number Description International Comfort Products part number 4 Hig...

Страница 30: ......

Страница 31: ...T 4 Jacket panel door GWA052 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 431223450WT 431223451WT 431223452WT 431223453WT 431223454WT 431223455WT Item number Description International Comfort Products pa...

Страница 32: ......

Страница 33: ...rt number Standing pilot Natural gas components 1 Gas valve 1 2 x 1 2 GWA052 through GWA175 Gas valve 3 4 x 3 4 GWA210 and GWA245 Honeywell Robertshaw Honeywell VR8200A2116 7200ER VR8300C4050 51104436...

Страница 34: ......

Страница 35: ...after the model number designates natural gas The letter after the N designates the pilot ignition system S for standing pilot or I for spark ignited pilot For example a suffix NS means a natural sta...

Страница 36: ......

Отзывы: