![ICP DAS USA M-7024 Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159092.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
92
2.19 $AA7N
Description:
Performs a 10 V calibration on a specified channel.
Syntax:
$AA7N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be calibrated (00 to FF)
7
Command for the 10 V calibration
N
Specifies the channel to be calibrated, zero based
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $0170
Response: !01
Performs a 10 V output calibration on channel 0 of
module 01 and returns a valid response.
Related Commands:
Section 2.8 $AA1N, Section 2.11 $AA3NVV
I-7022, M-7022