![ICP DAS USA M-7024 Скачать руководство пользователя страница 133](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159133.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
133
2.41 ~AA4N
Description:
Reads the safe analog output value of a specified channel
of a module.
Syntax:
~AA4N[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be read (00 to FF)
4
Command to read the safe analog output value
N
The channel to be read, zero based
Response:
Valid command :
!AA(Data)[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
(Data)
The safe analog output value, see Section 1.11
for details of the data format.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: ~0141
Response: !0105.000
Reads the safe analog output value of channel 1 of
module 01 and returns 05.000.
I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Содержание M-7024
Страница 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Страница 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Страница 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Страница 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...