I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
55
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command
?
Delimiter for an invalid command. If the
Baud
Rate
or
checksum
settings are changed without
connecting the INIT* terminal to ground, the
module will return an invalid command.
AA
Address of the module in hexadecimal format (00
to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: %0102300600
Response: !02
Changes the address of module 01 to 02. The module
returns a valid response.
Command: %0101300A00
Response: ?01
Changes the Baud Rate of module 01 to 115200bps.
The module returns an invalid command, because it
is not in INIT* mode.
Command: %0101300A00
Response: !01
Changes the Baud Rate of module 01 to 115200bps
and the module is in INIT* mode. The module
returns a valid response.
I-7021, I-7021P, I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028