I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
30
I-7022/M-7022 Voltage Output Calibration
1.
Connect a voltage meter to the voltage output channel
0 terminal of the module.
Short the current output terminal for the read-back
requirement
2.
Warm up the module for at least 30 minutes.
3.
Set the type code to 2, 0 ~ 10 V. Refer to Section 2.24
for details.
4.
Send command to output 10 V. Refer to Section. 2.15
for details.
5.
Repeat to send the trim command and check the meter
until the meter’s reading is nearest to 10 V. Refer to
Section 2.18 for details of sending the trim command.
6.
Send the 10 V calibration command. Refer to Section
2.21 for details.
7.
Repeat steps 1 to 9 for channel 1.
Note:
The M-7022 must be switched to the DCON protocol mode
before calibrating. Refer to Section 1.12.1 for details of the
switching protocol.