I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
54
2.1 %AANNTTCCFF
Description:
Sets the configuration of an analog output module.
Syntax
:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
Address of the module to be configured in
hexadecimal format (00 to FF)
NN
New address of the module in hexadecimal format
(00 to FF)
TT
New type code, see Section 1.11 for details. For
the I-7022, M-7022, M-7024U and M-7028, this
field should be set to 3F, 00 for M-7024U and
M-7208, and use the $AA9NTS command to set
the type of each channel, see Section 2.24 for
details.
CC
New Baud Rate code, see Section 1.11 for details.
The module must be switched to INIT* mode in
order to change Baud Rates. See Section A.1 for
details.
FF
Used to set the data format, checksum, and slew
rate settings (Section 1.11). For the I-7022,
M-7022, M-7024U and M-7208, use the
$AA9NTS command to set the slew rate of each
channel, see Section 2.24 for details. The module
must be switched to INIT* mode in order to
change the checksum setting. See Section A.1 for
details.
I-7021, I-7021P, I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Содержание M-7024
Страница 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Страница 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Страница 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Страница 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...