I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
165
Address Description
Attribute
40492
Host watchdog timeout count, write 0
to clear
R/W
40494
Slew rate
R/W
00257
Protocol, 0: DCON, 1: Modbus RTU R/W
00260
Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to
clear host watchdog timeout status
R/W
00261
1: enable, 0: disable host watchdog
R/W
00269
Modbus data format, 0: hex, 1:
engineering
R/W
00270
Host watch dog timeout status, write 1
to clear host watch dog timeout status
R/W
00272
Write 1 to load factory default
calibration parameters. for firmware
version A3.0 and later
W
00273
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
R
Output Types
Type Code Output Range
Data Format
Max
Min
30
0 ~ 20 mA
Engineering
20000
0
Hexadecimal
3FFFh
0000h
31
4 ~ 20 mA
Engineering
20000
4000
Hexadecimal
3FFFh
0000h
32
0 ~ 10 V
Engineering
10000
0
Hexadecimal
3FFFh
0000h
33
-10 ~ 10 V
Engineering
10000
-10000
Hexadecimal
3FFFh
C000h
34
0 ~ 5 V
Engineering
5000
0
Hexadecimal
3FFFh
0000h
35
-5 ~ 5 V
Engineering
5000
-5000
Hexadecimal
3FFFh
C000h
Содержание M-7024
Страница 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Страница 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Страница 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Страница 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...