I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
172
Analog Output Types
Type Code
Range
Data Format
Minimum
Maximum
0
0 mA ~ +20 mA
Engineering
0
+20000
Hexadecimal
0000h
FFFFh
1
+4 mA ~+20 mA
Engineering
+4000
+20000
Hexadecimal
0000h
FFFFh
2
0V ~ +10 V
Engineering
0
+10000
Hexadecimal
0000h
FFFFh
3
+/-10 V
Engineering
-10000
+10000
Hexadecimal
8000h
7FFFh
4
0 V ~ +5 V
Engineering
0
+5000
Hexadecimal
0000h
FFFFh
5
+/-5 V
Engineering
-5000
+5000
Hexadecimal
8000h
7FFFh