iKAN Series Display User Manual v 1.0.1 Page: 81
4.2.3.
Inserting float-type Variables into a Message
The iKAN display device provides Modbus registers for 64 float variables, allowing the Host PC or
a PLC to read or write data via the Modbus TCP/ RTU protocol. These values can also be inserted
into a message. If these values are modified via a remote Host or a PLC, the value will be
automatically refreshed when it is displayed on the iKAN series device.
The format for using a variable in a message is a 5-byte string, as follows:
1
2
3 to 5
Delimiter
Character
Variable Type
Modbus Address:
3-digit decimal number
%
f: Float variable (-3.4E+38 to +3.4E+38)
X
X
X
A maximum of 64 float variables can be stored on the iKAN series device, and are accessed using
Modbus register addresses 40000 to 40063.
Modbus
Address
Length
Description
Value Range
Attribute
Decimal
Hex.
40128
:
40255
0080
:
00FF
64
Float-type variables
3.4E+38 to +3.4E+38
R/W