![background image](http://html1.mh-extra.com/html/icp-das-usa/ikan-series/ikan-series_user-manual_3565344075.webp)
iKAN Series Display User Manual v 1.0.1 Page: 75
4.2.1.2.
Displaying the Current Date and Time
Modbus register addresses 30012 to 30020 can be used to read the current date and time value.
The following is an overview of how to read these values.
Modbus Address
Length
Description
Value
Range
Attribute
Decimal
Hex.
30012
000C
1
Year
0 to 9999
R
30013
000D
1
Month
1 to 12
R
30014
000E
1
Day
1 to 31
R
30015
000F
1
Abbreviated day of the week:
SUN, MON, TUE, WED, THU, FRI, SAT
0 to 6
R
30016
0010
1
Day of the week:
Sunday, Monday, Tuesday,
Wednesday, Thursday, Friday,
Saturday
0 to 6
R
30017
0011
1
Day of the week in Chinese
characters:
日、一、二、三、四、五、六
0 to 6
R
30018
0012
1
Hours (24-hour format)
0 to 23
R
30019
0013
1
Minutes
0 to 59
R
30020
0014
1
Seconds
0 to 59
R