I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
77
2.28. $AACnT
Description:
This command is used to read the status of the PWM hardware
trigger of a specific channel.
Syntax:
$AACnT[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be read (00 to FF)
Cn
Specifies the channel to be read
T
The command to read the PWM hardware trigger
Response:
Valid Command:
!AAS[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
(An invalid command is returned if the specified
channel is incorrect)
AA
The address of the responding module (00 to FF)
S
0: The hardware trigger is disabled
1: The trigger start is enabled
2: The trigger stop is enabled
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.