I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
22
Response:
Valid Command:
!AA[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command
?
Delimiter for an invalid command
(If the Baud Rate or checksum settings are changed
without switching the rear slide switch to the INIT
position, the module will return an invalid command.)
AA
The address of the module in hexadecimal format (00
to FF)
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.
Examples:
Command:
%0102500600
Response:
!02
Changes the address of module 01 to 02 and the module returns a
valid response.
Command:
%0202520600
Response:
!02
Sets the type of module 02 to 52 (Virtual Battery Backup) and the
module returns a valid response.