I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
55
2.17. $AA9(Data)
Description:
This command is used to send data to the LED display.
Syntax:
$AA8[CHKSUM](CR)
$
Delimiter character
AA
The address of the module where the data is to be sent
(00 to FF)
The command to send data to the LED display
(Data)
5 decimal 1 decimal point
(Max. = 99999. , Min. = 0.0000 )
Response:
Valid Command:
!AA[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
(An invalid command is returned if the specified
channel is incorrect.)
AA
The address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.