I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
146
3.3.7. Sub-function 42 (0x2A) Write miscellaneous settings
This sub-function code is used to set the miscellaneous settings of a
module.
Request
00
Address
1 Byte
1 to 247
01 Function
code 1
Byte
0x46
02
Sub-function code
1 Byte
0x2A
03 Miscellaneous
settings
1 Byte
The checksum settings and
the input range settings of
the module, see Section
1.7 for details
Note:
Reserved fields are filled with zeros.
Response
00
Address
1 Byte
1 to 247
01 Function
code 1
Byte
0x46
02
Sub-function code
1 Byte
0x2A
03 Miscellaneous
settings
1 Byte
0: OK
Others: error
Error Response
00
Address
1 Byte
1 to 247
01 Function
code 1
Byte
0xC6
02
Exception code
1 Byte
03: Reserved bits should
be filled with zeros, or an
incorrect number of bytes
were received