ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-88 -
Step 4: Configure the I/O Pair connection on the ET-2260 #2 module
1.
In the eSearch Utility, select
ET-2260 #2 module
and then click the “
Web
” button to launch the
browser program and connect to the web server.
2.
Enter the password in the Login password field
(the default password is “Admin”)
, and then
click the
“Submit”
button to display the configuration page.
3.
Click the
“Pair
” tab to display the I/O Pair-connectionSettings page.
Refer to Figures 5-1.3 to 5-1.4 for illustrations of how to perform the above procedure.
4. In the “I/O Pair-connection Settings”, select
“PUSH”
from the “
Mode
” drop-down options.
5. Enter the
IP address for ET-2260 #1 module
in the “
Remote IP
” field.
6. Enter the
TCP Port for ET-2260#1 module
in the “
Remote Port
” field.
7. Enter a
DI Count Value for ET-2260 #2 module
in the “
DI Count
” field (Local DI to Remote DO).
For example, enter
“1”
in the
“DI Count”
field. This means
DI x1 of ET-2260 #2 module
is mapped
to
DO1 x of ET-2260 #1 module
.
8. Select
Modbus protocol (e.g., “TCP”)
from the
“TCP/UDP”
drop-down options.
9. Click the “
Submit
” button to complete the configuration.
Figure 5-2.4
Содержание ET-2200 Series
Страница 20: ...ET 2200 Series Ethernet I O Modules Copyright 2020 ICP DAS CO Ltd All Rights Reserved 20 ET 2251 ET 2254 2254P...
Страница 21: ...ET 2200 Series Ethernet I O Modules Copyright 2020 ICP DAS CO Ltd All Rights Reserved 21 ET 2255 ET 2255U...
Страница 22: ...ET 2200 Series Ethernet I O Modules Copyright 2020 ICP DAS CO Ltd All Rights Reserved 22 ET 2260 ET 2261...
Страница 23: ...ET 2200 Series Ethernet I O Modules Copyright 2020 ICP DAS CO Ltd All Rights Reserved 23 ET 2261 16 ET 2268...