CAN-2084C
User’s Manual (Version 1.00, Sep/2018) ------------- 25
Input Signal Model Entry
Idx
Sidx
Description
Type
Attr
Default
3008h
0h
Number of entries
UNSIGNED 8
RW
8h
1h
Channel 0 input signal type
UNSIGNED 8
RW
1
…
…
…
…
…
8h
Channel 7 input signal type
UNSIGNED 8
RW
1
Note: 0 = TTL , 1 = Isolated (default)
3.2
Store and Restore Object
The user can write the value 65766173h to object with index 1010h and
subindex 1 to save the application setting, or write the value 64616F6Ch to the object
with index 1011h and subindex 1 and reboot the module to load the factory default.
The following table lists the relative objects which will be stored or restored after
writing these two objects. The factory default for these objects is also shown below:
Index Subindex
Description
Factory
Default
2004h
1~8
Counter type code for channel 0 ~ 7
03h
3000h
1~8
Counter value
0
3001h
1~8
Overflow value
0
3002h
1~8
Clear counter value
--
3003h
1~8
Edge mode
0
3004h
1~8
Frequency mode
0
3005h
1~8
Frequency time out value
BB8h
3006h
1~8
Low pass filter
0
3007h
1~8
Low pass filter time
1
3008h
1~8
Input signal model
1
Содержание CAN-2084C
Страница 4: ...CAN 2084C User s Manual Version 1 00 Sep 2018 4 Figure 1 1 CAN 2084C...
Страница 8: ...CAN 2084C User s Manual Version 1 00 Sep 2018 8 2 Hardware 2 1 Structure Top View Bottom View...
Страница 11: ...CAN 2084C User s Manual Version 1 00 Sep 2018 11 2 4 PIN Assignment...
Страница 35: ...CAN 2084C User s Manual Version 1 00 Sep 2018 35...
Страница 36: ...CAN 2084C User s Manual Version 1 00 Sep 2018 36...