Linkage control wiring diagram and parameter setting requirements
•
Linkage control is not used by default when the unit leaves the factory. If the user needs to use linkage
control, turn
【
Toge Switch
】
into
【
Enab
】
.
•
After the linkage control takes effect, when the linkage terminal of the unit is closed and the switch key
command is "open," the unit can run. When the unit linkage terminal is disconnected, the unit will stop.
•
When controlling the main module, the linkage switch only needs to be connected to the main module,
not to the slave module.
•
Terminal linkage switch signal can only be a passive signal, namely on and off signal. It cannot access
active signal, such as voltage signal, otherwise it will damage the electric control board. The company
shall not be responsible any main board damage due to improper operation of the terminal linkage
switch.
The connection mode is as shown below: