The heat pump has three modes of energy level adjustment when it is running. The principle is to calculate the
load required by the system based on the current temperature of the water tank and the set temperature, so as
to turn on the corresponding number of compressors. When the required compressor is turned on, it enters the
"energy adjustment during normal operation". At this time, as the water temperature rises, the number of
compressors to be turned on/off is adjusted according to the difference between the current temperature of the
water tank and the set temperature.
Single Unit Operation
When the unit is enabled, the calculation method of the number of compressors to be opened is as followed:
Heating: Nneed
=(
Thset
-
T
)×
Cmax
/
Tmax
Nneed: number of compressors to be enabled;
T: temperature of the control object;
Cmax: number of total compressors in the system;
Tmax: [temperature difference needed of enabling all compressors, 6
℃
by default];
THSET: [heating target temperature] or [hot water target temperature].
During operation, there are 4 temperature conditions for LOADING, HOLDING, UNLOADING, URGENCY
STOP.
T
HSET
: Setting temperature of heating mode
T
ULD
: Temperature differential of unloading
T
LD
: Temperature differential of loading
LOADING: When the object temperature is in this area, turn on a compressor every 60 seconds until all
compressors are turned enabled.
HOLDING: When the object temperature is in this area, unit keeps running and has no actions.
UNLOADING: When the object temperature is in this area, turn off a compressor every 60 seconds until all
compressors are turned off.
URGENCY STOP: When the object temperature is in this area, turn off a compressor per second until all
compressors are turned off.
Multiple Units Operation
Multiple unit operation follows the same rules for operation, with each water heater providing additional stages
of heating.
Содержание ccHPWH Series
Страница 11: ...8 III Product specification 1 Dimensions Unit inch ccHPWH275 S ccHPWH275 D ...
Страница 12: ...9 ccHPWH550 S ccHPWH550 D ...
Страница 26: ...23 2 Wiring diagram ccHPWH275 S ccHPWH275 D ...
Страница 27: ...24 ccHPWH550 S ccHPWH550 D ...
Страница 42: ...39 Schematic diagram of control wiring and code dialing of each module ...