BACnet / Boilers
Table 37. Lock and Hold Codes
Code
Description
Recommended Troubleshooting of Lockout Codes
151
High fire switch ON
OEM Specific
1. Check wiring and correct any potential wiring errors.
2. Check High Fire Switch to assure proper function (not welded or jumpered).
3. Manually drive the motor to the High Fire position and adjust the HF switch
while in this position and verify voltage through the switch to the HFS input with
a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.
152
Combustion pressure ON
OEM Specific
1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to make sure it is working correctly.
3. Reset and sequence the relay module.
4.
During STANDBY and PREPURGE, measure the voltage between Terminal
J6-5 and L2 (N). Supply voltage should be present. If not, the lockout switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
153
Combustion Pressure Off
154
Purge Fan switch On
OEM Specific
1. Purge fan switch is on when it should be off.
155
Purge Fan switch Off
156
Combustion pressure and Flame ON
OEM Specific
1.
Check that flame is not present in the combustion chamber. Correct any errors.
2.
Make sure that the flame detector is wired to the correct terminal.
3.
Make sure the F & G wires are protected from stray noise pickup.
4.
Reset and sequence the module, if code reappears, replace the flame detec
-
tor.
157
Combustion pressure and Flame OFF
158
Main valve ON
OEM Specific
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the module.
159
Main valve OFF
160
Ignition ON
OEM Specific
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the module.
161
Ignition OFF
162
Pilot valve ON
OEM Specific
1. Check Pilot Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the module.
163
Pilot valve OFF
164
Block intake ON
OEM Specific
1. Check wiring and correct any errors.
2.
Inspect the Block Intake Switch to make sure it is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across the switch. Supply
voltage should be present. If not, the Block Intake Switch is defective and
needs replacing.
5. If the fault persists, replace the relay module.
165
Block intake OFF
166-171
RESERVED
Feedback Codes
172
Main relay feedback incorrect
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
173
Pilot relay feedback incorrect
174
Safety relay feedback incorrect
175
Safety relay open
176
Main relay ON at safe start check
177
Pilot relay ON at safe start check
178
Safety relay ON at safe start check
179-183
RESERVED
Parameter Faults
184
Invalid BLOWER/HSI output setting
1.
Return to Configuration mode and recheck selected parameters, reverify and
reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
185
Invalid Delta T limit enable setting
186
Invalid Delta T limit response setting
187
Invalid DHW high limit enable setting
188
Invalid DHW high limit response setting
189
Invalid Flame sensor type setting
190
Invalid interrupted air switch enable setting
191
Invalid interrupted air switch start check enable setting
192
Invalid igniter on during setting
193
Invalid ignite failure delay setting
Содержание Mirius