![ICC Mirius Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/icc/mirius/mirius_installation-instructions-manual_3359219010.webp)
10
MEMBRANE SWITCH STYLE DISPLAY INSTALLATION
HIGH EFFICIENCY WATER HEATER INSTALLATION
Follow the directions under general guidelines for connecting the
module to the Energy Management System and power. This
section will guide the installer on how to mount and connect the
module to the water heater.
The control box and mounting location on the water heater is on
the top of the unit behind the display module. See
.
Figure 20. Locating the Control Box
Removal of the top is not required. Use a ladder to access the top
of taller water heaters. Locate the back of the display as shown in
. Disconnect the RJ45 plug from the display and connect
the RJ45 plug from the split communication cord into the display
receptacle. Plug the display communication cord back into the
receptacle on the split communication cord as shown in
Plug the supplied wiring harness with the gateway controller into
the remaining open RJ45 port on the Split Communication cord.
Figure 21. Locating the Back of the Display
Figure 22. Reconnecting the Communication cord to the Receptacle
Next locate the upper temperature probe and exhaust switch. See
.
Position the module between the two about 1 inch from
the central burner opening. See
.
For the 500 MBTUH
model this would be next to the upper temperature probe.
Figure 23. Locating Upper Temperature Probe and Exhaust Switch
Figure 24. Connecting the Communications Cable to the Module
Connect the three wires from the end of the communication cable
to the module in accordance with
. Once the unit is
installed and connected, the building management system can be
connected to the appropriate connection point on the module.
COMMERCIAL ELECTRIC WATER HEATER INSTALLATION
Follow directions in
for connecting the
module to the Energy Management System and power. This
section will guide the installer on how to mount and connect the
module to the water heater.
The module should be located where it will not interfere with the
door or in a location that is acceptable to the customer. Care
should be exercised to avoid drilling the self tapping screws into
electrical or sensitive components. Electrical power should be
disconnected before proceeding with ICC installation.
Using a flat blade screwdriver, loosen the screws holding the door
of the unit. See
Swing the door to the open position and locate the back of the
Figure 25. Loosening the Screws to the Door of the Unit