BACnet / Electric Water Heaters
Table 22. BACnet/Electric Water Heaters Object List
BACnet
Object Name
(Description)
BACnet
Object
Type/Inst.
BACnet
Object
Property
R/W
Units
Min
Value
(if W)
Max
Value
(if W)
Tank Temperature
(Controlling (Tank) Temperature)
Analog Input 5
Present_Value
R
ºC
Lower Temperature
(Lower or Secondary Temperature)
Analog Input 4
Present_Value
R
ºC
Tank Temperature
(Controlling Tank Temperature algorithmically
calculated)
Analog Input 5
Present_Value
R
ºC
Temper Setpoint
(Desired Tank Temperature)
Analog Value 201
Present_Value
R/W
ºC
(ºF)
32.2
(90)
82.2
(180)
Differen’lBank1
(Differential Setpoint Bank 1)
Analog Value 202
Present_Value
R/W
°C
(°F)
.6
(1)
11.1
(20)
Differen’lBank2
(Differential Setpoint Bank 2)
Analog Value 203
Present_Value
R/W
°C
(°F)
.6
(1)
11.1
(20)
Differen’lBank3
(Differential Setpoint Bank 3)
Analog Value 204
Present_Value
R/W
°C
(°F)
.6
(1)
11.1
(20)
Differen’lBank4
(Differential Setpoint Bank 4)
Analog Value 205
Present_Value
R/W
°C
(°F)
.6
(1)
11.1
(20)
Differen’lBank5
(Differential Setpoint Bank 5)
Analog Value 206
Present_Value
R/W
°C
(°F)
.6
(1)
11.1
(20)
Number of Cycles
(Number of heating cycles)
Analog Value 209
Present_Value
R
Number
Elapsed Time
(Time heater has been powered up in Hours
with two place beyond the decimal)
Analog Value 210
Present_Value
R
Hours with two
places beyond the
decimal.
Elapsed Days
(The number of days that the heater has been
powered up)
Analog Value 211
Present_Value
R
Days
Elapsed Hours
(The hours portion that the heater has been
powered up. Use with Elapsed Days)
Analog Value 212
Present_Value
R
Hours
Heating Time
(Time heater has been actually heating water
in Hours with two place beyond the decimal)
Analog Value 213
Present_Value
R
Hours with two
places beyond the
decimal.
Heating Days
(The amount of time in number of days heater
has been actually heating water)
Analog Value 214
Present_Value
R
Days
Heating Hours
(The hour’s portion of the amount of time
heater has been actually heating water. Use
with Heating Days)
Analog Value 215
R
R
Hours
#CCB HW Faults
(CCB Hardware Fault Counter)
Analog Value 217
Present_Value
R
Number
#Model Faults
ETH-1000 ONLY
(Model Fault Counter)
Analog Value 218
Present_Value
R
Number
#Temp Probe Faults
(Temperature Probe Fault Counter)
Analog Value 219
Present_Value
R
Number
#CCB Comm Faults
ETH-1000 only
(Communication Fault Counter)
Analog Value 223
Present_Value
R
Number
#ECO Faults
(High temperature Energy Cut Off switch in
Upper temperature probe Fault Counter)
Analog Value 224
Present_Value
R
Number
#Powr Anode Flts
(Powered Anode Alert Counter)
Analog Value 233
Present_Value
R
Number
#Element Faults
(Element Fault Counter)
Analog Value 234
Present_Value
R
Number
#LWCO Faults
(Low Water Cut Off Fault Counter)
Analog Value 235
Present_Value
R
Number
#Element Banks Used
(Number of Element Banks in Water Heater)
Analog Value 236
Present_Value
R
Number
1. Data is encoded into the 16 bits as major revision (upper 8 bits) and minor revision (lower 8 bits).