Document Revision: 1.A
Date: 7/18
T18060
FieldServer ENOTE
ProtoNode, ProtoCarrier or ProtoCessor
Recovery Instructions
Страница 1: ...Document Revision 1 A Date 7 18 T18060 FieldServer ENOTE ProtoNode ProtoCarrier or ProtoCessor Recovery Instructions ...
Страница 2: ... type 2 If the FieldServer was received before June 2018 the FieldServer is model type 1 However model type 1 FieldServers are still being shipped so a visual check of the ProtoCessor board is needed to confirm the model type of a FieldServer Check the images below for confirmation of the FieldServer model type Model Type 1 Standard Left and LonWorks Right ProtoCessors Model Type 2 Standard Left a...
Страница 3: ... LED to start flashing NOTE See Run LED location below When the Run LED starts flashing remove the jumper The unit IP Address will be set to 192 168 2 100 Open a browser window on a PC connected to the local network and download the config firmware img files for the application LED Locations for Standard Left and LonWorks Right ProtoCessors ProtoNode with Jumper Set for Recovery ...
Страница 4: ...us for any technical support needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email support sierramonitor com EMEA Support Information 44 2033 1813 41 Email support emea sierramonitor com ...