  RECOVERY INSTRUCTIONS 

 

Put a  jumper  on  the  first  and  second  pins  shown  on  the  left  side  of  the  Ethernet  port  as  shown 
below: 

                    

 

 

Wait for 1 to 2 minutes for the Run LED to start flashing. 

NOTE:  See Run LED location below: 

 

 

When the Run LED starts flashing, remove the jumper. 

 

The unit IP Address will be set to 192.168.2.100. 

 

Open  a  browser  window  on  a  PC  connected  to  the  local  network  and  download  the 
config/firmware/img files for the application. 

 

LED Locations for Standard (Left) and LonWorks (Right) ProtoCessors 

ProtoNode with Jumper Set for Recovery 