While waiting up to 20 minutes for the library manager to initialize and enter the
Auto/Online mode, go to“Library Manager Action – The Library Manager
Recovers (MVS/BLTS Environment)”.
Dual Library Manager Configuration:
For a dual library manager configuration
no library manager corrective action is needed. The standby library manager
automatically begins switching control from the active library manager which will
take approximately 10 minutes to complete. See Figure 168.
If the active library manager is not responding and the standby library manager
does not indicate it is switching to active after 5 minutes (see Figure 167 on
page 264), perform the above steps for a single library manager on the one that
failed.
While waiting for the library manager to initialize and go to AUTO/ONLINE mode, go
to “Library Manager Action – The Library Manager Recovers (MVS/BLTS
Environment)”.
Library Manager Action – The Library Manager Recovers
(MVS/BLTS Environment)
Single Library Manager Configuration:
For a single library manager, do the
following:
1. Wait for the library manager to be reinitialized and enter Auto/Online mode. This
may take up to 20 minutes to reinitialize.
2. If the failure occurred while inserting cartridges into the high-capacity I/O facility,
do not remove the cartridges. Leave the cartridges in place and the operation
will restart automatically. Cartridges inserted in the Convenience I/O station that
remain in the station will need to be removed from the station and then
re-inserted after the library manager re-initializes.
3. If the library manager reflects Auto/Online status, it has recovered. Contact the
service representative for a recoverable library manager error. Continue with
“BTLS Host Action” on page 268.
4. If the library manager does not reflect Auto/Online status and more than 30
minutes has elapsed since the re-initialization began, then contact the service
representative for a non-recoverable library manager error.
5. When the repair action is completed and the library is available to be varied
online, continue with “BTLS Host Action” on page 268.
Dual Library Manager Configuration:
For a dual library manager, do the
following:
1. Wait until the switch over completes and the standby library manager has
become the active library manager. The switch over takes approximately 10
Figure 168. Library Manager Switching Window
Chapter 8. Problem Determination Procedures
267
|
|
|
|
Содержание Tape Library Magstar 3494
Страница 1: ...Magstar 3494 Tape Library Operator Guide GA32 0280 09 IBM...
Страница 2: ......
Страница 3: ...Magstar 3494 Tape Library Operator Guide GA32 0280 09 IBM...
Страница 20: ...xviii Magstar 3494 Tape Library Operator Guide...
Страница 22: ...xx Magstar 3494 Tape Library Operator Guide...
Страница 27: ...A 0 6 C 0 0 4 1 Figure 2 Control Unit Frame Functional Components 3490E Front View Chapter 1 Introduction 5...
Страница 52: ...30 Magstar 3494 Tape Library Operator Guide...
Страница 62: ...40 Magstar 3494 Tape Library Operator Guide...
Страница 84: ...62 Magstar 3494 Tape Library Operator Guide...
Страница 106: ...84 Magstar 3494 Tape Library Operator Guide...
Страница 280: ...258 Magstar 3494 Tape Library Operator Guide...
Страница 326: ...304 Magstar 3494 Tape Library Operator Guide...
Страница 358: ...336 Magstar 3494 Tape Library Operator Guide...
Страница 374: ...352 Magstar 3494 Tape Library Operator Guide...
Страница 377: ......
Страница 378: ...IBMR Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber GA32 0280 09...