v
If the test fails, replace the fiber cable.
v
If the test is successful, go to step 6.
6.
Check the Fibre Channel cable connection at the server.
7.
Using a device driver utility such as
ntutil
or
tapeutil
, verify that the drive is
properly configured and available at the server.
8.
If the problem persists, the fault may be with the server's hardware or software.
Refer to your server's service manual.
9.
When the problem is corrected (or determined to be a server problem), restore
all of the fiber cables to their correct position.
Fixing a Consistent Error with Multiple Drives on a Fibre
Channel Loop
Use the following procedure to determine if all of the drives on the Fibre Channel
have the problem:
1.
Use a device driver utility (such as
ntutil
or
tapeutil
) to verify that the drive is
available and properly configured at the server.
2.
Determine the type of Fibre Channel topology that you are using.
3.
Using this guide or the service guides of associated switch, hub, or fiber
products, try to isolate which part of the Fibre Channel Storage Area Network
(SAN) is experiencing problems.
4.
Perform one of the following:
v
If the problem exists on a small number of drives, go to “Fixing a Consistent
Error with a Single Drive on a Fibre Channel Loop” on page D-55.
v
If the problem exists with a large number of drives, perform the following
steps:
a.
Disconnect all except one failing drive on the Fibre Channel.
b.
Run the Fibre Channel wrap test to determine if a failure occurs on that
drive (see Function Code 6 in “Function Code 6: Run Host Interface Wrap
Test” on page D-32). If it does, perform the procedure in “Fixing a
Consistent Error with a Single Drive on a Fibre Channel Loop” on page
D-55.
c.
Continue to connect one drive at a time to the Fibre Channel loop.
5.
When the problem is corrected, restore all of the Fibre Channel cables to their
correct position.
Fixing a Consistent Error in a Point-to-Point Topology
1.
Ensure that the tape drive is powered ON.
2.
Verify that the tape drive's serial number is the same as the drive serial number
that the server program is using.
3.
Ensure that the drive is connected to the host or switch. The drive must be able
to detect light and communicate with the server.
4.
Run the Fibre Channel wrap test at the drive's Fibre Channel connector (see
Function Code 6 in “Function Code 6: Run Host Interface Wrap Test” on page
D-32).
v
If the test fails, replace the tape drive.
v
If the test is successful, go to step 5.
5.
Run the Fibre Channel wrap test at the end of the fiber cable (see Function
Code 6 in “Function Code 6: Run Host Interface Wrap Test” on page D-32).
v
If the test fails, replace the fiber cable.
D-56
TS3310 Tape Library Maintenance Information
Содержание System Storage TS3310
Страница 2: ......
Страница 6: ...iv TS3310 Tape Library Maintenance Information...
Страница 8: ...vi TS3310 Tape Library Maintenance Information...
Страница 18: ...xvi TS3310 Tape Library Maintenance Information...
Страница 20: ...xviii TS3310 Tape Library Maintenance Information...
Страница 22: ...xx TS3310 Tape Library Maintenance Information...
Страница 28: ...1 6 TS3310 Tape Library Maintenance Information...
Страница 70: ...1 Home Sensor Flag a66mi080 1 Figure 3 11 Home Sensor Flag 3 8 TS3310 Tape Library Maintenance Information...
Страница 76: ...3 14 TS3310 Tape Library Maintenance Information...
Страница 92: ...4 16 TS3310 Tape Library Maintenance Information...
Страница 196: ...6 94 TS3310 Tape Library Maintenance Information...
Страница 242: ...7 46 TS3310 Tape Library Maintenance Information...
Страница 300: ...1 2 a66mi015 Figure 8 58 Guide rollers on Y axis Picker Assembly 8 58 TS3310 Tape Library Maintenance Information...
Страница 378: ...8 136 TS3310 Tape Library Maintenance Information...
Страница 382: ...9 4 TS3310 Tape Library Maintenance Information...
Страница 390: ...10 8 TS3310 Tape Library Maintenance Information...
Страница 396: ...A 6 TS3310 Tape Library Maintenance Information...
Страница 414: ...Control Module and Expansion Module Electrical System a66mi037 C 6 TS3310 Tape Library Maintenance Information...
Страница 415: ...Library Electrical Block a66mi038 Appendix C Library Diagrams C 7...
Страница 416: ...Library Control Blade a66mi042 C 8 TS3310 Tape Library Maintenance Information...
Страница 417: ...Library Control Blade Functions a66mi039 Appendix C Library Diagrams C 9...
Страница 418: ...Accessor Control Block a66mi040 C 10 TS3310 Tape Library Maintenance Information...
Страница 421: ...a66mi036 Appendix C Library Diagrams C 13...
Страница 422: ...Library Cables Library System Grounding a66mi041 C 14 TS3310 Tape Library Maintenance Information...
Страница 423: ...Library Power System a66mi044 Appendix C Library Diagrams C 15...
Страница 424: ...a66mi043 C 16 TS3310 Tape Library Maintenance Information...
Страница 484: ...D 60 TS3310 Tape Library Maintenance Information...
Страница 494: ...E 10 TS3310 Tape Library Maintenance Information...
Страница 498: ...F 4 TS3310 Tape Library Maintenance Information...
Страница 504: ...G 6 TS3310 Tape Library Maintenance Information...
Страница 520: ...H 16 TS3310 Tape Library Maintenance Information...
Страница 526: ...X 6 TS3310 Tape Library Maintenance Information...
Страница 529: ......
Страница 530: ...Part Number 46X4072 Printed in USA GA32 0478 08 1P P N 46X4072...
Страница 531: ...Spine information IBM System Storage TS3310 Tape Library TS3310 Tape Library Maintenance Information Machine Type 3576...