18
IBM NeXtScale System Planning and Implementation Guide
As with iDataPlex servers, NeXtScale servers support S3 mode. S3 allows
systems to come back into full production from low-power state much quicker
than a traditional power-on. In fact, cold boot normally takes about 270 second;
with S3, it takes only 45 seconds. When you know that a system will not be used
because of time of day or state of job flow, you can send it into a low-power state
to save power and, when needed, bring it back online quickly.
In Table 2-1, the features of IBM NeXtScale System are compared to those
features of IBM iDataPlex.
Table 2-1 Comparing IBM NeXtScale System to IBM iDataPlex
Feature
iDataPlex
NeXtScale
Comments
Form factor
Unique rack
1200 mm x 600 mm
Standard rack
600 mm x 1100 mm
NeXtScale System allows for
lower-cost racks and, perhaps, racks
customers already have.
Density in a
standard 42U rack
Up to 42 servers
Up to 84 servers (72 with
space for switches)
NeXtScale System can provide up to
twice the server density when both
types of servers are installed in a
standard 42U rack.
Density in two
consecutive floor
tiles
a
a. Here we compare the density of servers that can be fitted in a single row of racks while using top-of-rack
switches. We use a single iDataPlex rack for iDataPlex servers that is 1200 mm wide, and we compare it with
two standard racks for NeXtScale servers that also are 1200 mm wide.
84 servers
8 ToR switches
(iDataPlex rack)
144 servers
12 ToR switches
(two standard racks next to
each other)
NeXtScale can provide up to 71%
more servers per row when using
top-of-rack (ToR) switches.
Density/400 sq. ft.
(with Rear Door
Heat Exchanger)
1,680 servers
84 servers/iDataPlex
rack; four rows of five
racks
2,160 servers
72 servers/standard rack;
three rows of 10 racks
10x10 floor tiles
28% density increase because of
standard rack layout.
Power/tile (front)
22 kW maximum
15 kW typical
42 s switches
37 kW maximum
25 kW typical
72 s switches
Similar power/server
GPU support
Two GPUs per server in
2U
Two GPUs per server in 1U
effective space (GPU
support planned)
GPU tray + base node = 1U.
NeXtScale System has twice the
density of iDataPlex.
Direct attached
storage
None
b
b. None available with Intel E5-2600 v2 series processor.
Other storage-rich
offerings that are planned
include eight drives in 1U
effective space
More flexibility with NeXtScale
storage plan.
Direct water cooling
Available Now
NeXtScale System design
supports water cooling
Opportunity to optimize cost with
NeXtScale.
Содержание NeXtScale System
Страница 2: ......
Страница 16: ...xiv IBM NeXtScale System Planning and Implementation Guide...