enough so that the height of the installed fastener does not exceed 65 mm
(2.5 in.). This maximum height ensures that the fastener can fit under the
rack.
The following examples provide descriptions of nonraised floor fastener sets:
v
Threaded hole insert that is secured into the concrete floor and a bolt (with a
washer) that screws into the insert
v
Threaded stud that is secured into the concrete floor with a nut (with a
washer) that screws over it
Figure 26 on page 158 shows illustrations of the example fastener sets.
2.
Work with your consultant or structural engineer and use the following
guidelines to install the fasteners in the concrete floor:
v
Use Figure 27 to determine the placement of the fasteners.
v
Ensure that the installed fasteners do not exceed a height of 65 mm (2.5 in.)
from the floor. This maximum height ensures that the fastener can fit under
the rack.
v
Ensure that the installation allows the fasteners to meet the required pull
force after they are installed (2400 lb pull force).
v
If you use a threaded bolt that secures into a threaded insert in the floor and
the bolt extends longer than 30 mm (1.2 in.), which is the thickness of the
load plate, consider using a jam nut and a washer on the shaft of the bolt so
that the load plate can be secured snugly to the floor. Talk to your consultant
or structural engineer to determine whether a jam nut is necessary.
FRAME OUTLINE
f2c00813
FRAME FRONT
FRAME OUTLINE
416.1 (16.4)
882.1 (34.7) FRAME TO FRAME SPACING
FRAME REAR
FRAME REAR
CABLE OPENING
IN FRAME
CABLE OPENING
IN FRAME
FASTENERS
BASE RACK
EXPANSION RACK
FRAME FRONT
609.6
(24.0)
227.0
(8.9)
304.8 (12.0)
304.8 (12.0)
FASTENERS
Figure 27. Locations for fastener installation (nonraised floor). The pattern repeats for up to
five models. Dimensions are in millimeters (inches).
Chapter 6. Meeting DS8000 series delivery and installation requirements
159
Содержание DS8700
Страница 1: ...IBM System Storage DS8800 and DS8700 Version 6 Release 3 Introduction and Planning Guide GC27 2297 09...
Страница 2: ......
Страница 3: ...IBM System Storage DS8800 and DS8700 Version 6 Release 3 Introduction and Planning Guide GC27 2297 09...
Страница 8: ...vi Introduction and Planning Guide...
Страница 10: ...viii Introduction and Planning Guide...
Страница 20: ...xviii Introduction and Planning Guide...
Страница 22: ...xx Introduction and Planning Guide...
Страница 44: ...22 Introduction and Planning Guide...
Страница 142: ...120 Introduction and Planning Guide...
Страница 160: ...138 Introduction and Planning Guide...
Страница 212: ...190 Introduction and Planning Guide...
Страница 218: ...196 Introduction and Planning Guide...
Страница 224: ...202 Introduction and Planning Guide...
Страница 242: ...220 Introduction and Planning Guide...
Страница 254: ...232 Introduction and Planning Guide...
Страница 255: ......
Страница 256: ...Printed in USA GC27 2297 09...