Power Checkout
Use the following procedure for diagnosing power
problems for the IBM PC Server Rack Enclosure and IBM
Netfinity Rack enclosure (Type 9306).
Attention
For Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX
only:
Ensure that the voltage selector switch on each
server installed in the server rack is set to 230 V
ac.
For Models 200, 900 only:
Ensure that the voltage selector switch on each
server installed in the server rack is set to the
proper voltage as supplied by the Power
Distribution Unit, PDU.
001
– Ensure the external power cord is in good condition and
properly connected to a known-good power source.
– Ensure the internal power cables are in good condition
and properly connected. (The internal power cables
connect between the power distribution unit and the
servers installed in the server rack.)
– Ensure the following devices are powered on.
1. Power distribution unit
2. Server selector unit
3. All system units
4. Display
ARE ALL THE ABOVE ITEMS/CONDITIONS OK?
Yes No
002
Correct the problem and verify correct operation of
the server rack.
003
– Using the server selector keypad buttons, check for
correct operation of all the servers installed in the rack.
DID THE FAILURE OCCUR ON MORE THAN ONE
SERVER?
Yes No
004
Go to the Hardware Maintenance manual for the
server that was selected when the failure occurred
and run the server diagnostic programs.
(Step 004 continues)
4
IBM PC Server/Netfinity Racks HMM
Содержание 9306 001
Страница 2: ......
Страница 8: ...vi IBM PC Server Netfinity Racks HMM...
Страница 14: ...6 IBM PC Server Netfinity Racks HMM...
Страница 32: ...24 IBM PC Server Netfinity Racks HMM...
Страница 35: ...Front Cover Type 9306 Model 001 27...
Страница 38: ...Note The maximum server weight is 77 kg 170 lb 30 IBM PC Server Netfinity Racks HMM...
Страница 40: ...32 IBM PC Server Netfinity Racks HMM...
Страница 42: ...Side Panel Locked Unlocked 34 IBM PC Server Netfinity Racks HMM...
Страница 47: ...Blank Bezel Fixed Shelf Type 9306 Model 200 39...
Страница 60: ...Parts Listing Type 9306 Model 200 1 2 3 5 6 7 8 9 4 10 52 IBM PC Server Netfinity Racks HMM...
Страница 62: ...54 IBM PC Server Netfinity Racks HMM...
Страница 64: ...Side Panel Locked Unlocked 56 IBM PC Server Netfinity Racks HMM...
Страница 69: ...Blank Bezel Fixed Shelf Type 9306 Model 900 61...
Страница 82: ...Parts Listing Type 9306 Model 900 1 10 11 2 3 4 5 6 7 8 9 74 IBM PC Server Netfinity Racks HMM...
Страница 101: ...Parts Listing Type 9308 Model 42P 42X 1 2 3 4 5 6 7 Type 9308 Model 42P 42X 93...
Страница 121: ......
Страница 122: ...IBM Part Number 09N1031 Printed in U S A S83H 9585 4...