AS1029MP-CL
Page
4
FITTED WITH MODEL WS1 VALVE/EI CONTROL
Check the equipment upon arrival for damage or shortages and report same to our Office or Agent before
starting.
Position the Softener on a firm foundation, preferably concrete, with sufficient space for operation and
maintenance. The softener must be within One and a Half metres of a 240V-10 amp Power Outlet. The
softener
MUST
be installed under cover and protected from the weather as the Valve control and Transformer
are not waterproof.
STEP 1
The Softener is supplied with the resin preloaded in the tank and the valve/ bypass assembled
on the tank.
STEP 2
Connect the Inlet and Outlet pipes and Drain line to the control valve as per the instruction
book installation details.
Note the directional arrows on the Valve. The inlet is on the right
hand side
facing the front of the valve
. The drain is from the larger elbow on the top of the
valve. The valve Inlet and Outlet threads are 25mm BSP Female with a 12mm push on Hose
connection for the drain line.
STEP 3
Remove front lid from the cabinet. Then connect cabinet brine overflow drain line to waste
trap.
STEP 4
Load 2 bags of 25kg high purity water softener salt into the brine tank and replace lid.
STEP 5
Refer to Instruction booklet for start up procedure (placing conditioner into Service")
NOTE: The INLET PIPE connection is on the right hand side as viewed
from the front of the valve.
NOTE: The POWER connection transformer socket is on the right hand
side as viewed from the front of the valve at the back of the
control.
Table 3
MODEL
RESIN LITRES
BRINE TANK - SALT
LOADING KG
AS1029MP-CL
29
50
BASIC INSTALLATION
OF
IBC CABINET WATER SOFTENER SYSTEM
Содержание AS1029MP-CL
Страница 3: ...AS1029MP CL Page 3...
Страница 5: ...AS1029MP CL Page 5...
Страница 11: ...AS1029MP CL Page 11 MODEL AS1029MP WATER SOFTENER WITH CONTROL VALVE SERIES MODEL WS1EI...
Страница 19: ...AS1029MP CL Page 19...
Страница 20: ...AS1029MP CL Page 20 WS1EI Screen Display Information And Programming Instructions...
Страница 22: ...AS1029MP CL Page 22 General Regeneration Error Screens Status...
Страница 29: ...AS1029MP CL Page 29 SPARE PARTS AND SERVICING INSTRUCTIONS...
Страница 38: ...AS1029MP CL Page 38 10 V3156 O ring 214 2 Flow Diagrams Service and Backwash flow diagram service...
Страница 39: ...AS1029MP CL Page 39 flow diagram backwash Flow Diagram Downflow...
Страница 40: ...AS1029MP CL Page 40 flow diagram downflow brine Flow Diagrams Rinse and Fill...
Страница 41: ...AS1029MP CL Page 41 flow diagram rinse flow diagram fill WS1 Wrench Order No V3193 01...
Страница 49: ...AS1029MP CL Page 49 INJECTOR PERFORMANCE CURVES...
Страница 50: ...AS1029MP CL Page 50...
Страница 52: ...AS1029MP CL Page 52...