AS1029MP-CL
Page
8
SUGGESTED SETTINGS
(VOLUME THROUGHPUT IN CUBIC METRES Based on Maximum Exchange Capacity )
TABLE 2
Raw Water Hardness
mg/L CaCO
3
Maximum Program Setting
In Cubic Metres throughput
(see note)
60
33.5
80
25.0
100
20.0
120
16.5
140
14.5
160
12.5
180
11.0
200
10.0
250
8.0
Important Note:
To provide uninterrupted soft water
supply to the end of the service
and just before a regeneration is
due it is strongly recommended to
de-rate the throughput setting by
the average daily usage. Eg. If the
setting is elected at 20.0 then
deduct a figure of one days usage.
(Note:
Estimated
daily
consumption per person is 300
litres or 0.3Cubic Metres :- for 3
people = 0.9 cubic metres :-
deduct One Cubic Metre.)
For Commercial applications it will
be necessary to determine the
daily water usage figure.
For other raw water hardness multiply the throughput at 100 hard i.e. 20.0 by the ratio of 100 divided
by the desired hardness.
e.g. for 50 hard
=
20.0 x 100
=
40.00
50
e.g. for 170 hard
= 20.0 x 100
=
11.76 input 11.5
170
Note: The program for M
3
input will only accept the inputting of a whole or half a number. e.g. If the
calculated throughput is say 9.75m
3
then what can be programmed in is 9.5 or 10.0. However, always
select the lower figure i.e. 9.5 in this example. Above 50M³ the program will only accept increments in
2.5 , therefore only input a lower figure eg. Calculation gives 58.33 therefore input 57.5.
Note :- The chart is based on low to medium total dissolved solids water ,consult IBC Water for using the
softener for waters above 250 mg/L hardness.
Programming Parameters to be input at commissioning:
1. Throughput in cubic metres from Table 2.
2. Current time of day.
NOTE: All other parameters have been factory pre-set – DO NOT CHANGE.
MODEL AS1029MP-CL SOFTENER
THE MICROPROCESSOR CONTROL WILL REQUIRE BASIC DATA PROGRAMMING TO SUIT THE
RAW WATER HARDNESS AND DESIRED UNIT CAPACITY
IMPORTANT:
IT IS ESSENTIAL THAT YOU READ THE GENERAL CONDITIONER INFORMATION AND
CONTROL SETTINGS OF THIS MANUAL BEFORE ATTEMPTING TO SET THE FUNCTIONS OF THIS
UNIT. THE DEALER OR AGENT CAN SUPPLY THE RAW WATER HARDNESS
. HOWEVER DO NOT
EXCEED THE MAXIMUM THROUGH PUT IN CUBIC METERS BASED ON THE ACTUAL RAW WATER
HARDNESS FIGURE IN TABLE 2.
Содержание AS1029MP-CL
Страница 3: ...AS1029MP CL Page 3...
Страница 5: ...AS1029MP CL Page 5...
Страница 11: ...AS1029MP CL Page 11 MODEL AS1029MP WATER SOFTENER WITH CONTROL VALVE SERIES MODEL WS1EI...
Страница 19: ...AS1029MP CL Page 19...
Страница 20: ...AS1029MP CL Page 20 WS1EI Screen Display Information And Programming Instructions...
Страница 22: ...AS1029MP CL Page 22 General Regeneration Error Screens Status...
Страница 29: ...AS1029MP CL Page 29 SPARE PARTS AND SERVICING INSTRUCTIONS...
Страница 38: ...AS1029MP CL Page 38 10 V3156 O ring 214 2 Flow Diagrams Service and Backwash flow diagram service...
Страница 39: ...AS1029MP CL Page 39 flow diagram backwash Flow Diagram Downflow...
Страница 40: ...AS1029MP CL Page 40 flow diagram downflow brine Flow Diagrams Rinse and Fill...
Страница 41: ...AS1029MP CL Page 41 flow diagram rinse flow diagram fill WS1 Wrench Order No V3193 01...
Страница 49: ...AS1029MP CL Page 49 INJECTOR PERFORMANCE CURVES...
Страница 50: ...AS1029MP CL Page 50...
Страница 52: ...AS1029MP CL Page 52...