Configuration
Update interval
Select the measurement interval here.
The following default intervals are available: 200 ms, 3 s, 10 s, 10 min or 2 h
If you choose a default interval, the Unit and Amount fields will show the matching
values and cannot be edited.
Custom
The “Custom” selection allows you to freely define the measurement interval us-
ing the Unit and Amount fields.
Select the unit from the dropdown menu.
Enter the amount (number of units) as an integer value into the field.
The defined amount and the unit determine the measurement interval and auto-
matically the name of the module.
Mode
Custom: Select “Custom” to configure the analog signals in the “Analog” tab to
your preferences.
Auto: Select “Auto” to show the additional line “Signals based on”. Click on the
arrow to open a dropdown menu that contains all submodules that have already
been created:
The submodules can be selected individually. The characteristic values config-
ured in them serve as the basis for the new measurement, however with the
measurement interval defined here.