14.
Each submodule has its own time base; the default value should not be changed.
The signal names in the submodules are already preset. They include the corre-
sponding characteristic value, the measuring input and the measurement interval al-
lowing it to be identified unambiguously in subsequent evaluations. The configuration
of the submodules is described in more detail in chapter 10.3.2
” and following chapters. Below you will find a summary of the
key properties and the determined characteristic values of the submodules according
to EN50160. (see also chapter 10.1.1
“Overview of the modules in ibaPDA”).
EN50160: Power frequency
- power frequency, interval 10 s
EN50160: Supply voltage variation
- RMS value voltage, interval 10 min
EN50160: Flicker severity
- long-term flicker (P
lt
) per phase, interval 2 h
EN50160: Supply voltage unbalance
- negative sequence unbalance, interval 10 min
EN50160: Harmonic voltage, for each voltage input, interval 10 min
- fundamental frequency, 10 min
- THD up to 40th harmonic
- relative harmonic 1 - 50
EN50160: Mains signalling voltage for each voltage input,
interval 3 s
- fundamental frequency
- relative harmonic DC
- relative harmonic 1
– 50
- relative interharmonic 1 - 50
EN50160: Voltage events, interval half period
- RMS value voltage, half period
15.
To calculate other parameters, click the “Click to add module...” link to add submod-
ules (Basic, Phasor, Power, Aggregation, Spectrum, Flicker severity, Unbalance,
Commutation notches, Events). For a detailed description of the submodules, read
Содержание PQU-S
Страница 93: ...Manual Issue 1 3 93 ibaPQU S and backplane Dimensions in mm Figure 63 Dimensions of ibaPQU S with backplane...
Страница 94: ...Manual ibaPQU S 94 Issue 1 3 Mounting plate 19 Dimensions in mm Figure 64 Dimensions of 19 mounting plate...
Страница 113: ...Manual Issue 1 3 113 Figure 74 Example of 1 phase measuring with a Rogowski coil or a current clamp...
Страница 115: ...Manual Issue 1 3 115 15 Certificate...