Manual
ibaPADU-S-IT-16
50
Issue 1.10
left under FiberOptics_IO as inputs or outputs. Depending on the FO protocol, there is a
maximum number of signals:
Link protocol
Max. number of signals
Rotary switch S1
External
1024 Integer or 512 Real
1 - F
3.3Mbit
64 I 64 Digital
0
32Mbit 50µs
64 I 64 Digital
0
32Mbit 100µs
128 I 128 Digital or
64 Real + 64 Digital
0
32Mbit 1000µs
1024 I 1024 Digital or
512 Real + 512 Digital
0
32Mbit Col
8x 3,3Mbit
– input links (see
above)
Any combination of Real and
Integer links
0
Use with ibaPDA:
Figure 38: Modular measuring system with intelligent pre-processing
In the example above, “External” has to be chosen as FO protocol for input and output.
The communication between ibaPADU-S-IT-16 and ibaPDA is done in the 32Mbit Flex
mode.
Figure 39: ibaLogic as module in ibaPDA
Important note
For the “External“ Link protocol, the S1 switch needs to be positioned on 1-F. For all other
settings S1 = 0.