Manual
ibaPADU-S-IT-16
18
Issue 1.10
Figure 4:
Connection diagram for digital inputs X5
7.5.2
Debounce filters
For the digital inputs, there are four debounce filters for each. These can be chosen and
configured for each signal independently. You have got the following filters at your dispos-
al:
„Off“ (without filter)
„Stretch rising edge“
„Stretch falling edge“
„Stretch both edges“
„Delay both edges“
For each filter, a debounce time has to be defined in µs. This debounce time can have a
value between
[1µs…65535µs].
Off
The measured input signal is transferred without filtering.