- 211 -
Figure 6-28 PID parameters switchover
PID deviation
PI
parameters
Group 1 of PID
parameters
PA
-19
PA
-20
PA
-05,
PA
-06,
PA
-07
PA
-15,
PA
-16,
PA
-17
Group 2 of PID
parameters
F
unction Code
Parameter Name
Setting Range
Default
P
A-21
PID initial value
0.0%–100.0%
0.0%
P
A-22
PID initial value holding time
0.00–650.00s
0.00s
When the AC drive starts up, the PID starts closed-loop algorithm only after the PID output
is fxed to the PID initial value (PA-21) and lasts the time set in PA-22.
Figure 6-29 PID initial value function
Output
frequency
PID initial value
PA
-21
PID initial value
holding time PA
-22
Time
F
unction Code
Parameter Name
Setting Range
Default
P
A-23
Maximum deviation between two PID
outputs in forward direction
0.00%–100.00%
1.00%
P
A-24
Maximum deviation between two PID
outputs in reverse direction
0.00%–100.00%
1.00%
This function is used to limit the deviation between two PID outputs (2 ms per PID output) to
suppress the rapid change of PID output and stabilize the running of the AC drive.
PA-23 and PA-24 respectively correspond to the maximum absolute value of the output
deviation in forward direction and in reverse direction.
I5300 User Manual Description of Function Codes
Содержание I5300 Series
Страница 8: ......
Страница 9: ...1 Safety Information and Precautions ...
Страница 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Страница 17: ...2 Product Information ...
Страница 28: ...Product Information I5300 User Manual 28 ...
Страница 29: ...3 Mechanical and Electrical Installation ...
Страница 45: ...4 Operation Display and Application Examples ...
Страница 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Страница 79: ...5 Function Code Table ...
Страница 135: ...6 Description of Function Codes ...
Страница 247: ...7 EMC ...
Страница 255: ...8 Selection and Dimensions ...
Страница 261: ...9 Maintenance and Troubleshooting ...