Description of Function Codes
I5300 User Manual
- 162 -
Value
F
unction
Description
10
RUN pause
The AC drive decelerates to stop, but the running
parameters are all memorized, such as PLC, swing
frequency and PID parameters. After this function is
disabled, the AC drive resumes its status before stop.
11
Normally open (NO) input
of external fault
If this terminal becomes ON, the AC drive reports Err15
and performs the fault protection action.
F
or more
details, see the description of
P
9-47.
12
Multi-reference terminal 1
The setting of 16 speeds or 16 other references can be
implemented through combinations of 16 states of these
four terminals.
13
Multi-reference terminal 2
14
Multi-reference terminal 3
15
Multi-reference terminal 4
16
Terminal 1 for acceleration/
deceleration time selection
Totally four groups of acceleration/deceleration time can
be selected through combinations of two states of these
two terminals.
17
Terminal 2 for acceleration/
deceleration time selection
18
F
requency source
switchover
The terminal is used to perform switchover between two
frequency sources according to the setting in
P
0-07.
19
UP and DOWN setting
clear (terminal, operation
panel)
If the frequency source is digital setting, the terminal
is used to clear the modi
fi
cation by using the UP/
DOWN function or the increment/decrement key on the
operation panel, returning the set frequency to the value
of
P
0-08.
20
Command source
switchover terminal
If the command source is set to terminal control (
P
0-02
= 1), this terminal is used to perform switchover between
terminal control and operation panel control.
If the command source is set to communication control
(
P
0-02 = 2), this terminal is used to perform switchover
between communication control and operation panel
control.
21
Acceleration/Deceleration
prohibited
It enables the AC drive to maintain the current frequency
output without being affected by external signals (except
the STOP command).
22
PID pause
PID is invalid temporarily. The AC drive maintains
the current frequency output without supporting PID
adjustment of frequency source.
23
PLC status reset
The terminal is used to restore the original status of
PLC control for the AC drive when PLC control is started
again after a pause.
24
Swing pause
The AC drive outputs the central frequency, and the
swing frequency function pauses.
25
Counter input
This terminal is used to count pulses.
26
Counter reset
This terminal is used to clear the counter status.
27
Length count input
This terminal is used to count the length.
28
Length reset
This terminal is used to clear the length.
Содержание I5300 Series
Страница 8: ......
Страница 9: ...1 Safety Information and Precautions ...
Страница 16: ...Safety Information and Precautions I5300 User Manual 16 ...
Страница 17: ...2 Product Information ...
Страница 28: ...Product Information I5300 User Manual 28 ...
Страница 29: ...3 Mechanical and Electrical Installation ...
Страница 45: ...4 Operation Display and Application Examples ...
Страница 78: ...Operation Display and Application Examples I5300 User Manual 78 ...
Страница 79: ...5 Function Code Table ...
Страница 135: ...6 Description of Function Codes ...
Страница 247: ...7 EMC ...
Страница 255: ...8 Selection and Dimensions ...
Страница 261: ...9 Maintenance and Troubleshooting ...