OIM AI-7X82D V2.1 Page 8 of 10

TABLE 4 :

 Below listed points will appear only if O/P2 is selected as an Alarm mode. In Alarm mode, Controller 

continuously compares PV with either SP (for deviation or Band -alarm) or an independent Alarm set points (for 
process high and process low alarm). HYS2 in Control list decides when to switch OFF the Alarm. 

Low Alarm : OP2 activates when PV<SP2.

OUTPUT-2 ON

OUTPUT-2 OFF

SP2

PV

SP2

OUTPUT-2 OFF

OUTPUT-2 ON

PV

High Alarm : OP2 activates when PV>SP2.

OUTPUT-2 OFF

OUTPUT-2 ON

SP2

PV

Direct acting

SP2

OUTPUT-2 ON

OUTPUT-2 OFF

PV

Reverse acting

Band Alarm : OP2 activates when PV falls outside the band w.r.t. SP1 in either 
direction.

OUTPUT ON

OUTPUT ON

PV

SP1

SP2

SP2

OUTPUT OFF

OUTPUT OFF

OUTPUT OFF

PV

SP1

SP2

SP2

OUTPUT ON

User can select direct Alarm Logic in which OP2 will be ON under alarm condition; 
otherwise OFF (used for audio visual alarm).   

User  can  select  Reverse  Alarm  Logic  in  which  OP2  will  be  ON  in  normal 
conditions & will be OFF under alarm conditions (used to trip the process in alarm 
conditions).

If  this  parameter  is  set  as  ‘YES’  & Alarm  condition  persists,  it  will  Disable Alarm 
O/P at power ON.

If this parameter is set as ‘NO’ & Alarm condition persists, it will Enable Alarm O/P 
at power up.

Once the Alarm is activated, User has following three options to de-activate it.
When PV falls within  the programmed limits The Alarm will be de-activated 
automatically.

Once the alarm is activated, it remains activated until acknowledged manually by  
UP key.

Once the alarm is activated, it can be de-activated either by pressing UP key  or 
when PV falls within the alarm limits.

If Enabled, User can View & edit the Alarm Set point in USER list. 

If disabled, User can not View or edit Alarm Set Point in USER list.

High Deviation Alarm : OP2 activates when PV is greater than SP1 ± set 
deviation value

OUTPUT ON

PV

SP1

OUTPUT OFF

OUTPUT OFF

+Ve
 dev

PV

Sp1

OUTPUT ON

Low Deviation Alarm : OP2 activates when PV is less than SP1 ± set deviation 
value

OUTPUT OFF

PV

OUTPUT ON

OUTPUT ON

PV

OUTPUT OFF

SP2

SP2

SP2

SP2

OUTPUT ON

PV

SP1

OUTPUT OFF

OUTPUT ON

PV

OUTPUT OFF

SP2

SP2

OUTPUT OFF

PV

SP1

OUTPUT ON

OUTPUT OFF

PV

OUTPUT ON

SP2

SP2

-Ve

 dev

+Ve
 dev

+Ve
 dev

+Ve
 dev

-Ve

 dev

-Ve

 dev

-Ve

 dev

ALARM
  TYPE

ALARM
 LOGIC

ALARM
INHIBIT

ALARM
  ACK.

ALARM
   SET
 POINT

Low

Direct

No

Auto

Enable

  PARA
METER

 UPPER
DISPLAY

 LOWER
DISPLAY

DESCRIPTION

DEFAULT

AI-7682D

Содержание AI-7482D

Страница 1: ...rent power cables Where it is impractical to do this use shielded ground at both ends v The controller should not be wired to a 3 Phase supply with unearthed star connection Under fault condition such...

Страница 2: ...NC OUT2 RLY 90 270VAC SSR BZR OP1 OP2 Digital Input AI 7782D OUT 1 RLY NO CM NC OUT 2 RLY NO CM NC SSR BZR OP1 OP2 90 270VAC Digital Input AI 7982D AI 7682D 7882D OUT 1 RLY SSR BZR OP1 OP2 1 2 3 4 5...

Страница 3: ...LOWER DISPLAY UPPER DISPLAY RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters 0 0 to 100 0 Th...

Страница 4: ...for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously...

Страница 5: ...PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD...

Страница 6: ...ated By selecting this parameter Digital Input can be used as Water Level Indicator input By selecting this parameter Digital Input can be used to detect whether the door is open or closed By selectin...

Страница 7: ...logic for control Output 2 in which OP2 will remain ON till PV SP2 PV increases when output is ON User can select Cool logic for control Output 2 in which OP2 will remain ON till PV SP2 PV decreases...

Страница 8: ...S Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has follo...

Страница 9: ...the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3...

Страница 10: ...ired P I D values It can be performed at any time after power ON but it is best to start it when the process is at Ambient temperature in order to minimize overshoot undershoot Auto tuning is applied...

Отзывы: