MECHANICAL  INSTALLATION

The label on the controller identifies the serial number, wiring connections and batch number.

CAUTION: 

To prevent the risk of electrical shock, switch off the power before making/removing any connection or removing 

the controller from  its enclosure.

OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)

C

H

MODEL : AI - 7682D

E

D

C

H

A

B

F

G

PANEL

CUTOUT

A

B

D

C

H

E

G

F

MODEL:- AI - 7482D/ 7782D/ 7982D  

PANEL

CUTOUT

MODEL : AI - 7882D

B

A

E

D

G

F

PANEL

CUTOUT

INSTALLATION GUIDELINES :

1.  Prepare the cut-out with proper dimension as shown in figure.      
2.  Remove clamp from controller 
3.  Push  the  controller  through  panel  cut-out  and  secure  the 

controller in its place by tightening the side clamp.

TABLE : 1

Model

Dim

48 

72

96

96

48

48 

72

96

48

96

8    

10

10

10   

10

75 

65

45

45

45

44

68

92

44

92

44

68

92

92

44

9

9

9

9

9

A

B

H

C

D

F

G

E

43

66

89

89

43

AI-7482D

AI-7782D

AI-7982D

AI-7682D

AI-7882D

FRONT PANEL LAYOUT

4

5

6

7

1

2

3

AI-7482D

OP1

OP2

SOAK

PV

SV

SET

AT

RESET

START

AI-7482D

6

7

4

5

1

2

3

OP1

OP2

SOAK

PV

SV

-therm

i

AI-7782D

SET

AT

RESET START

AI-7782D

6

7

4

5

1

2

3

OP1

OP2

SOAK

PV

SV

TUNE

SET

AT

RESET

START

-therm

i

AI-7982D

AI-7982D

1

5

3

2

6

4

7

SET

START

AT

RESET

PV

SV

AI-7682D

OP2

SOAK

OP1

AI-7682D

1

2

4

3

6

7

5

PV

SV

AI-7882D

OP1

OP2

SOAK

SET

START

AT

RESET

AI-7882D

ELECTRICAL INSTALLATION

The electrical connection diagram is shown on the controller enclosure as below.

NO CM NC

OUT1 - RLY

NO CM NC

OUT2 - RLY

90~270V

AC

SSR | BZR

OP1 | OP2

Digit

al

Input

AI-7782D

OUT 1 - RLY

NO CM NC

OUT 2 - RLY

NO CM NC

SSR | BZR

OP1 | OP2

90~270VAC

Digital

Input

AI-7982D

AI-7682D/7882D

OUT 1 - RLY

SSR | BZR

OP1 | OP2

1

2

3

4

5

6

7

8

9

10

11 12

NO CM NC

NO CM NC

13 14 15 16 17 18

L

N

SUPPLY

Digital

Input

OUT 2 - RLY

AI-7482D

NO

CM

NC

Digit

al

Input

CM

NC

NO

OUT2

90~270VAC

OUT1-RLY

OUT1-SSR

FRONT PANEL LAYOUT DESCRIPTION :

Glows when OP1 is ON & flashes when delay time (dly1) is in operation (if selected mode is ON-
OFF)

Glows when OP2 is ON & flashes when alarm condition persists even after acknowledged OR 
delay time (dly2) is in operation & selected mode is ON-OFF.

Glows when Soak mode is selected & flashes when soak timer is in operation.

(1) For SP programming. (2) To access Control mode. (3) To access Configuration mode along 
with UP key. (4) To scroll the parameter & to store its value.

(1) To increase/alter parameter value in program mode. (2) To enter in configuration mode (with 
SET key). (3) To acknowledge Alarm. (4) To enter in tune mode (with DOWN key). 

(1) To decrease/alter parameter value in program mode. (2) To enter in tune mode (with UP key). 

It will display (1) Measured value of selected input or Error messages in run mode. (2) Parameters 
value in program mode.

It will display (1) SP (Main set point) / SP2 (Auxiliary/Alarm) set value / Set Soak time value/ 
balance or elapsed soak time in run mode. (2) Parameter code in program mode. 

1

2

3

4

5

6

7

Sr. 

NAME

FUNCTION

(1) To increase/alter parameter value in program mode with Up / Dn key.
(2) Press for 3sec in programming, this will help to go back to previous parameter.

OP1 LED

OP2 LED

SOAK LED

 UPPER
DISPLAY
 LOWER
DISPLAY

SET
KEY

SHIFT
  KEY

 UP
KEY

DOWN
  KEY

AI-7682D

Содержание AI-7482D

Страница 1: ...rent power cables Where it is impractical to do this use shielded ground at both ends v The controller should not be wired to a 3 Phase supply with unearthed star connection Under fault condition such...

Страница 2: ...NC OUT2 RLY 90 270VAC SSR BZR OP1 OP2 Digital Input AI 7782D OUT 1 RLY NO CM NC OUT 2 RLY NO CM NC SSR BZR OP1 OP2 90 270VAC Digital Input AI 7982D AI 7682D 7882D OUT 1 RLY SSR BZR OP1 OP2 1 2 3 4 5...

Страница 3: ...LOWER DISPLAY UPPER DISPLAY RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters 0 0 to 100 0 Th...

Страница 4: ...for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously...

Страница 5: ...PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD...

Страница 6: ...ated By selecting this parameter Digital Input can be used as Water Level Indicator input By selecting this parameter Digital Input can be used to detect whether the door is open or closed By selectin...

Страница 7: ...logic for control Output 2 in which OP2 will remain ON till PV SP2 PV increases when output is ON User can select Cool logic for control Output 2 in which OP2 will remain ON till PV SP2 PV decreases...

Страница 8: ...S Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has follo...

Страница 9: ...the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3...

Страница 10: ...ired P I D values It can be performed at any time after power ON but it is best to start it when the process is at Ambient temperature in order to minimize overshoot undershoot Auto tuning is applied...

Отзывы: