: Normally Close terminal of relay

NO

: Normally  Open terminal of relay   

OP1

: Output 1 

OP2

: Output 2

C.A. 

: Control Action   

CJC 

: Cold junction compensation 

CM

: Common terminal of relay    

LWC

: Lead wire (Length)-  

              compensation

SP1

: Set Point Value (set temp.) 

PV

: Process Value (actual Tmp.)  

SSR

: Solid State Relay

T/C

: Thermocouple

ABBREVIATION :

TEMP (°C)

SP

AMB

O/P

HYSTERISIS

ON

ON

ON

OFF

OFF

HEAT LOGIC/ ON-OFF

TIME

Fig : 3.1

TEMP (°C)

SP

AMB

O/P

O/P

HYSTERISIS

ON

ON

ON

OFF

OFF

TIME

Fig : 3.2

COOL LOGIC/ ON-OFF

USER GUIDE 

: -

ON-OFF ACTION :

 In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to the set point value. On 

reaching to SP, Output turns OFF & remains OFF till actual temperature drops down (in Heat Logic) or raises (in Cool Logic) 
equal to hysterisis set by user. (As shown in Fig. 3.1 & 3.2)

AUTO TUNING MODE :

 In this mode, Controller learns the  process characteristics by itself and calculates the required P,I & 

D  values. It can be performed at any time after power ON but, it is best to start it when the process is at Ambient temperature 
in order to minimize overshoot & undershoot. Auto tuning is applied in case of : 
(1) Initial set up for a new process. 
(2) Substantial change in SP from previous auto tuning value. 
(3) Control accuracy is not satisfactory. 
If the control performance by using auto-tuning is still unsatisfactory, User can apply further adjustments of P,I & D values as 
shown in Table:3 below.

Proportional Band

Integral Time

Derivative Time

Slow Response
Over Shoot or Oscillations
Slow Response
Instability or Oscillation
Slow Response or Oscillation
High Over Shoot

Decrease PB
Increase  PB
Decrease  Int
Increase  Int
Decrease  Dt
Increase  Dt

Adjust

Symptom

Solution

Table: 3

AUTO TUNING MODE : 

To enter in this mode, Press and hold SHIFT key for minimum 3 sec. 

This  function  will  be  executed  only  if  selected  control  action  is  PID  & Auto  tune  is 
Enable.
The  Auto-tuning  function  can  be  initiated  by  setting  this  parameter  to  YES.  The 
decimal  of  LSB  flashes  till  auto  tuning  function  is  in  progress.  During Auto-tuning, 
The controller learns the process characteristics by itself & calculates required P, I 
& D values.
User can cancel or abort this feature by setting this parameter to NO.

AUTO

TUNING

MODE

NO

  PARA
METER

 UPPER
DISPLAY

 LOWER
DISPLAY

DESCRIPTION

DEFAULT

AI-7682D

Содержание AI-7482D

Страница 1: ...rent power cables Where it is impractical to do this use shielded ground at both ends v The controller should not be wired to a 3 Phase supply with unearthed star connection Under fault condition such...

Страница 2: ...NC OUT2 RLY 90 270VAC SSR BZR OP1 OP2 Digital Input AI 7782D OUT 1 RLY NO CM NC OUT 2 RLY NO CM NC SSR BZR OP1 OP2 90 270VAC Digital Input AI 7982D AI 7682D 7882D OUT 1 RLY SSR BZR OP1 OP2 1 2 3 4 5...

Страница 3: ...LOWER DISPLAY UPPER DISPLAY RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters 0 0 to 100 0 Th...

Страница 4: ...for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously...

Страница 5: ...PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD...

Страница 6: ...ated By selecting this parameter Digital Input can be used as Water Level Indicator input By selecting this parameter Digital Input can be used to detect whether the door is open or closed By selectin...

Страница 7: ...logic for control Output 2 in which OP2 will remain ON till PV SP2 PV increases when output is ON User can select Cool logic for control Output 2 in which OP2 will remain ON till PV SP2 PV decreases...

Страница 8: ...S Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has follo...

Страница 9: ...the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3...

Страница 10: ...ired P I D values It can be performed at any time after power ON but it is best to start it when the process is at Ambient temperature in order to minimize overshoot undershoot Auto tuning is applied...