background image

i

4

OIM AI-7X82D V2.1 Page 4 of 10

0

 to

500 Sec.

o

1 to 25  C

o

1 to 25  C

50 %

 to 

100 %

0

 to

500 Sec.

This parameter will be prompted only if selected control action is ON - 
OFF. It sets the dead band between ON & OFF switching of the Output. 
Larger value of hysterisis minimize the number of ON-OFF operation to 
the load. This increases life of actuators like contactors but, also 
produces large errors (between PV & SV).

-9.9 

to

9.9°C

-9.9 

to

9.9°C

0

 to

99 Sec.

0.0

 to

99°C.

This  parameter  will  be  prompted  only  if  selected  control  action  is  ON  - 
OFF. It sets the main output Delay time where O/P once turned OFF will 
turn ON only after Delay time, regardless difference between PV & SP. 
Also, Delay will be considered at every power ON.

This parameter will be prompted only if Control Logic for Output1 is 
configured for Heat-Cool.
SP (set point) will be consider as (SP-Gap1) for heating.

This parameter will be prompted only if selected control mode for 
output2 is Auxiliary control or an Alarm. The value of this parameter sets 
the dead band between ON & OFF switching of output load.

 This parameter will be prompted only if Control Logic for Output1 is 
configured for Heat-Cool.
SP (set point) will be consider as (SP+Gap2) for cooling.

This  parameter  will  be  prompted  only  if  Output2  is  configured  as  an 
Auxiliary control output OR Control Logic is configured for Heat-Cool. In 
this mode, it sets the output Delay time where O/P once turned OFF will 
turn  ON  only  after  Delay  time,  regardless  difference  between  PV  & 
SP2. Also, Delay will be considered at every power ON.

This  parameter  will  be  prompted  only  if  selected  control  mode  for 
Output2 is Soak timer. Depending on end of soak strategy, the value of 
this parameter sets the activation time for OP2 when Soak timer is over. 
Setting this parameter to ‘0’ will make OP2 continuously ON at the end 
of Soak time till User starts the next cycle.

This parameter defines the permissible deviation of PV from SP during 
soak  time  cycle.  If  PV  falls  outside  the  Soak  band  during  soak  cycle, 
Timer  halts.  Timer  will  start  only  when  PV  falls  within  the  soak  band. 
This parameter is ignored if set to ‘0’.

This parameter will be prompted only if selected control action is PID. 
This parameter allows the User to carry out Auto Tuning function below 
the set point. (If tune offset is set to 50 %, tuning will be carried out at 
50 % of the set point and if set to 100 %, tuning will be carried out at 
100 % of the set point.)

  TUNE
OFFSET

CONTROL
     HYS

DELAY 1

DELAY 2

HYS 2

GAP 2

GAP 1

 SOAK
  TIME
DELAY

SOAK
BAND

100 %

2°C

2°C

120 Sec.

0°C

0°C

0 Sec.

10 Sec.

0 Sec.

  PARA
METER

 LOWER
DISPLAY

 UPPER
DISPLAY

RANGE

DESCRIPTION

DEFAULT

CONFIGURATION LIST :

   

(1) 

 key simultaneously 

To enter in this mode, press and hold SET & UP

for 3 sec. 

                                                  (2) Press UP or DOWN key to scroll between parameter options. 
                                                  (3) Press SET key to store current parameter & move on to the next parameter.

Set this parameter to 15 (Default LOCK CODE) to access Config. List.
User have a choice to set different Lock Code via USER LOCK CODE in Config. 
List.

Fe-k(J) T/C

Cr-AL(K) T/C

o

760 C

o

-99 

1300 C

o

-99 

1300 C

o

-99 

400 C

o

1  C

o

1  C

o

1  C

}

(R) T/C

(S) T/C

TC - N

TC - T

o

0 ~ 1700 C

o

0 ~ 1700 C

o

1  C

o

1  C

o

1  C

Sensor Type 

Accuracy

Resolution

Range

  

±

o

C

This parameter value is set according to the type of sensor (Thermocouple or RTD 
input) connected to the controller's input terminals. 

0

TC - J

LOCK
CODE

INPUT
 TYPE

 LOWER
DISPLAY

 UPPER
DISPLAY

  PARA
METER

DESCRIPTION

DEFAULT

AI-7682D

Содержание AI-7482D

Страница 1: ...rent power cables Where it is impractical to do this use shielded ground at both ends v The controller should not be wired to a 3 Phase supply with unearthed star connection Under fault condition such...

Страница 2: ...NC OUT2 RLY 90 270VAC SSR BZR OP1 OP2 Digital Input AI 7782D OUT 1 RLY NO CM NC OUT 2 RLY NO CM NC SSR BZR OP1 OP2 90 270VAC Digital Input AI 7982D AI 7682D 7882D OUT 1 RLY SSR BZR OP1 OP2 1 2 3 4 5...

Страница 3: ...LOWER DISPLAY UPPER DISPLAY RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters 0 0 to 100 0 Th...

Страница 4: ...for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously...

Страница 5: ...PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD...

Страница 6: ...ated By selecting this parameter Digital Input can be used as Water Level Indicator input By selecting this parameter Digital Input can be used to detect whether the door is open or closed By selectin...

Страница 7: ...logic for control Output 2 in which OP2 will remain ON till PV SP2 PV increases when output is ON User can select Cool logic for control Output 2 in which OP2 will remain ON till PV SP2 PV decreases...

Страница 8: ...S Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has follo...

Страница 9: ...the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3...

Страница 10: ...ired P I D values It can be performed at any time after power ON but it is best to start it when the process is at Ambient temperature in order to minimize overshoot undershoot Auto tuning is applied...

Отзывы: