Chapter 6 – Platform Management Option
0818D User’s Guide
6-5
Sensor No. Voltage
Resolution (10 bit)
Volt0 +3.3V 20
mV
Volt1
+5V
30 mV
Volt2 Battery
6V
40
mV
Volt3
-12V
53 mV
Volt4
+12V
80 mV
Volt5 and
Volt6
120V AC
-48V DC
2 V
0.5V
Volt7 +5V 36
mV
6.4.3 Fan Sensors
Fans 0, 1, and 2 are the three blowers located at the top of the card
cage. Fan 3, Fan 4, and Fan 5 each consist of a group of fans (total
of 10) located at the bottom of the card cage. In each of these lower
fan groups, if all of the fans are turning at an acceptable speed, the
sensor for that group reads 0. If any of the fans in the group are not
working, the sensor for that group will read 1. By default, a reading
of 1 on any of the digital fan sensor causes a minor alarm.
6.4.4 Power Supply Sensors
Power supply sensors detect the health of individual power supplies.
If a power supply is good, its sensor will read 0. A reading of 1
indicates that the power supply is not healthy. By default, this will
cause a major alarm.
6.4.5 IPMB Power
The +5V DC IPMB Power on the bus is regulated separately from the
rest of the CMC circuit. It is taken from +12 Vdc input and regulated
down to +5 Vdc. Optional battery backup is provided.
The IPMB Power is capable of supplying 1 ampere DC current at +5
Vdc per PICMG 2.9.
Voltage Tolerance: +5V +5%/-3% at backplane, 0A to 0.8A load or
with 500 mA hot swap transient.
The CMC board monitors its own IPMB power voltage. The IPMB
power voltage is shown as Volt7 in Table 6-1. Default SDR
Parameters. Any IPMB_PWR reading outside these thresholds will
set a Major Alarm.
Содержание 0818D
Страница 1: ...0818D User s Guide Doc No 1002830 Rev 3 User s Guide 0818D CompactPCI System ...
Страница 3: ...0818D User s Guide 3 ...
Страница 9: ...Table of Contents 0818D User s Guide 9 This page was intentionally left blank ...
Страница 10: ......
Страница 12: ...Chapter 1 Introduction 0818D User s Guide 1 2 This page was intentionally left blank ...
Страница 22: ......
Страница 36: ...Chapter 3 Hardware 0818D User s Guide 3 14 This page was intentionally left blank ...
Страница 42: ...Chapter 4 Power Distribution 0818D User s Guide 4 6 This page was intentionally left blank ...
Страница 44: ...Chapter 5 Software 0818D User s Guide 5 2 This page was intentionally left blank ...
Страница 61: ...Chapter 6 Platform Management Option 0818D User s Guide 6 17 This page was intentionally left blank ...
Страница 62: ......
Страница 78: ...Appendix 3 Limited Warranty 0818D User s Guide A3 2 This page was intentionally left blank ...
Страница 80: ...Appendix 4 FCC Information 0818D User s Guide A4 2 This page was intentionally left blank ...