SETUP
3-4
powermax
1650
Operator Manual
2
Locating the power supply
Locate the Powermax1650 power supply with at least 10 inches (0.25 m) of open space at the
front, back, and fan side of the power supply for proper ventilation.
Power connection
The Powermax1650 is a universal power supply that configures itself to operate with AC voltages
from 200 to 600 3PH (230-400 3PH for the CE model). Use a line disconnect switch for each
power supply so that the operator can turn off the power supply quick ly in an emergency. Locate
the switch so it is easily ac ces si ble to the operator. The interrupt level of the switch must be equal
to or ex ceed the continuous rating of the fuses. Use slow-blow fuses rated per local and national
electrical codes.
CSA model
Three-phase
Input voltage
200-208
230-240
400
480
600
Input current at 16kw output
53
46
27
22
21
Input current during arc stretch
75
72
42
34
33
Recommend fuse
80
80
50
40
40
CE model
Three-phase
Input voltage
230
400
Input current at 16kw output
46
27
Input current during arc stretch
72
42
Recomended fuse
80
50