Page 33
10.9 Functional check
»
Run the system with maximum out-
put for a couple of minutes
»
Check
all
safety devices.
»
Check hose connections and seals
for leakage.
10.10 Finishing maintenance
After finishing substantial maintenance work,
the service interval „Steam amount“ must be
reset (s. sections 3.5.2 und 3.8 in the „Con-
trol Standard“ manual).
To do so, follow the procedure below (use
the keys for changing the values dis-
played):
»
from standard display, select „P00“.
»
confirm with SET key.
»
input code „010“.
»
confirm with SET key.
»
change display from „1--“ to „3 --“
(select parameter group „Service“).
»
confirm with SET key.
•
„3-1“ is displayed
»
confirm with SET key.
»
change display from „0“ to „1“
(„Reset service interval“).
»
Confirm with SET key.
»
return to standard display by tou-
ching the ESC key twice.
The steam amount counter now again holds
the value preset (s. „3-3“ parameter, „Service
interval [t]“), that determines the next time for
maintenance when met.
<
<
„ / “