Page 17
7.2 Water supply
Foreign material in water supply pipe may
cause premature wear of the solenoid
valve.
Flush the water supply pipe before making
connection to the solenoid valve. This is of
particular importance in case of a newly
installed pipe.
»
Install a shut-off valve (AV) in the
supply line.
»
Install a water filter (WF) if required
due to bad water quality.
In case of no safety device for drinking water
protection according to DIN EN 1717 present
in the house installation system, a system
separator at least of the CA type or use of the
Hyflow retrofit option is mandatory.
Shut-off valve (SV) and water filter (WF) are
not included in the delivery.
For connection to the water supply line, the
water hose (56) with cap nuts on both ends
supplied with the unit may be used.
Make connection as follows:
»
Attach cap nut with inner seal ring to
inlet screw joint on the humidifier
housing and tighten.
Do not overtighten the cap nut!
Excessive tightening will destroy the fitting.
Strainer must be placed inside the solenoid
valve.
»
Screw the other hose end cap nut
with its inner seal on a customer-
provided water tap (cap nut internal
thread is ¾“) .
7.3 Water discharge
Risk of scalding!
During blow down up to 0.3 l/sec (.08 gal./
sec) are being drained with a temperature of
about 95 °C (203 °F).
Ensure that the drain hose is reliably fas-
tened and wastewater can drain freely and
pressureless.
Humidifier installation location and wastewa-
ter discharge must be on the same pressure
level.
127,&(
127,&(
3OHDVHQRWH
Water supply
100000 - 1000000 Pa
(14.5 - 145 psi)
3/4” connection
SV
3OHDVHQRWH
127,&(
127,&(
3OHDVHQRWH
:$51,1*
3OHDVHQRWH
Содержание MiniSteam MSE05